Assessment Year | 2008 |
---|---|
Principal Product | Blades for aerospace and power generation |
NAICS | 336412: Aircraft Engine and Engine Parts Manufacturing |
SIC | 3724: Aircraft Engines and Engine Parts |
Sales Range | $10 M to 50M |
# of Employees | 297 |
Plant Area |
240,000
ft2
|
Annual Production | 20,000
pieces
|
Production Hrs. Annual | 6,240
hrs
|
Location (State) | New York |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $1,318,351 | 18,574,451 |
kWh
|
$0.071 |
Electricity Demand | $214,526 | 33,046 |
kW-mo/yr
|
$6.49 |
Electricity Fees | $60,488 | - |
|
- |
Natural Gas | $285,670 | 28,771 |
MMBtu
|
$9.93 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $97,837 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $69,731 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Administrative Changes Savings | One-time Revenue or Avoided Cost Savings |
---|---|---|---|---|---|---|---|---|---|
01 | 2.4231: Reduce the pressure of compressed air to the minimum required | $15,465 | - |
$13,259
176,779
kWh
|
$2,206
-
kW-mo/yr
|
- | - | - | |
02 | 4.821: Pay bills on time to avoid late fees | $854 | - | - | - | - | $854 | - | |
03 | 2.4221: Install compressor air intakes in coolest locations | $22,823 | $1,071 |
$19,572
260,957
kWh
|
$3,251
-
kW-mo/yr
|
- | - | - | |
04 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $6,511 | $1,250 |
$5,583
74,443
kWh
|
$928
-
kW-mo/yr
|
- | - | - | |
05 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $310 | $385 |
$177
2,365
kWh
|
$19
-
kW-mo/yr
|
- | - | $114 | |
06 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $39,769 | $83,044 |
$34,097
454,460
kWh
|
$5,672
-
kW-mo/yr
|
- | - | - | |
07 | 2.6211: Conserve energy by efficient use of vending machines | $781 | $1,451 |
$781
10,408
kWh
|
- | - | - | - | |
08 | 2.7135: Install occupancy sensors | $318 | $674 |
$318
4,243
kWh
|
- | - | - | - | |
09 | 2.3212: Optimize plant power factor | $11,006 | $39,533 | - | - | $11,006 | - | - | |
TOTAL RECOMMENDED | $97,837 | $127,408 |
$73,787
983,655
kWh
|
$12,076
-
kW-mo/yr
|
$11,006 | $854 | $114 | ||
TOTAL IMPLEMENTED | $69,731 | $86,424 |
$59,747
796,468
kWh
|
$9,870
-
kW-mo/yr
|
- | - | $114 | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Administrative Changes Savings | One-time Revenue or Avoided Cost Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs