| Assessment Year | 2008 |
|---|---|
| Principal Product | Solenoids, Valves and LVDTs |
| NAICS | 335999: All Other Miscellaneous Electrical Equipment and Component Manufacturing |
| SIC | 3679: Electronic Components, Not Elsewhere Classified |
| Sales Range | $50 M to 100M |
| # of Employees | 420 |
| Plant Area |
324,284
ft2
|
| Annual Production | 3,000,000
pieces
|
| Production Hrs. Annual | 5,746
hrs
|
| Location (State) | New York |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $884,665 | 11,211,055 |
kWh
|
$0.079 |
| Electricity Demand | $5,518 | 27,590 |
kW-mo/yr
|
$0.20 |
| Natural Gas | $270,328 | 24,762 |
MMBtu
|
$10.92 |
| TOTAL YEARLY COSTS | - | |||
| RECOMMENDED SAVINGS* | $79,798 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | $23,506 | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Primary Raw Material Savings |
|---|---|---|---|---|---|---|---|
| 01 | 2.4322: Use or replace with energy efficient substitutes | $7,704 | - |
$7,584
96,000
kWh
|
$120
-
kW-mo/yr
|
- | |
| 02 | 2.4231: Reduce the pressure of compressed air to the minimum required | $664 | - |
$658
8,330
kWh
|
$6
-
kW-mo/yr
|
- | |
| 03 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $730 | - |
$726
9,193
kWh
|
$4
-
kW-mo/yr
|
- | |
| 04 | 2.7122: Disconnect ballasts | $209 | - |
$208
2,628
kWh
|
$1
-
kW-mo/yr
|
- | |
| 05 | 2.4314: Use synthetic lubricant | $187 | - |
$186
2,357
kWh
|
$1
-
kW-mo/yr
|
- | |
| 06 | 2.7122: Disconnect ballasts | $3,272 | $77 |
$3,255
41,199
kWh
|
$17
-
kW-mo/yr
|
- | |
| 07 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $6,466 | $1,031 |
$6,432
81,421
kWh
|
$34
-
kW-mo/yr
|
- | |
| 08 | 2.7135: Install occupancy sensors | $2,367 | $486 |
$2,367
29,965
kWh
|
- | - | |
| 09 | 2.4221: Install compressor air intakes in coolest locations | $5,959 | $2,060 |
$5,924
74,986
kWh
|
$35
-
kW-mo/yr
|
- | |
| 10 | 3.1191: Change procedures / equipment / operating conditions | $46,739 | $23,800 | - | - | $46,739 | |
| 11 | 3.5145: Recover and reuse spent acid baths | $1,453 | $2,062 | - | - | $1,453 | |
| 12 | 2.6211: Conserve energy by efficient use of vending machines | $185 | $353 |
$185
2,347
kWh
|
- | - | |
| 13 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $3,863 | $9,244 |
$3,843
48,645
kWh
|
$20
-
kW-mo/yr
|
- | |
| TOTAL RECOMMENDED | $79,798 | $39,113 |
$31,368
397,071
kWh
|
$238
-
kW-mo/yr
|
$48,192 | ||
| TOTAL IMPLEMENTED | $23,506 | $13,251 |
$23,390
296,086
kWh
|
$116
-
kW-mo/yr
|
- | ||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Primary Raw Material Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs