Assessment Year | 2006 |
---|---|
Principal Product | Books |
NAICS | 323111: Commercial Printing (except Screen and Books) |
SIC | 2732: Book Printing |
Sales Range | $10 M to 50M |
# of Employees | 414 |
Plant Area |
291,000
ft2
|
Annual Production | 26,000,000
units
|
Production Hrs. Annual | 6,240
hrs
|
Location (State) | New York |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $808,975 | 9,755,345 |
kWh
|
$0.083 |
Electricity Demand | $61,783 | 20,579 |
kW-mo/yr
|
$3.00 |
Electricity Fees | $3,981 | - |
|
- |
Natural Gas | $250,734 | 23,746 |
MMBtu
|
$10.56 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $127,989 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $56,169 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Natural Gas Savings | One-time Revenue or Avoided Cost Savings |
---|---|---|---|---|---|---|---|---|---|
01 | 2.6218: Turn off equipment when not in use | $25,842 | - |
$21,807
262,734
kWh
|
$4,035
-
kW-mo/yr
|
- | - | - | |
02 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $2,166 | - |
$2,025
24,398
kWh
|
$141
-
kW-mo/yr
|
- | - | - | |
03 | 2.4314: Use synthetic lubricant | $721 | - |
$673
8,112
kWh
|
$48
-
kW-mo/yr
|
- | - | - | |
04 | 2.2437: Recover waste heat from equipment | $11,490 | $813 | - | - | - |
$11,490
-
MMBtu
|
- | |
05 | 2.4221: Install compressor air intakes in coolest locations | $11,107 | $228 |
$10,573
127,380
kWh
|
$534
-
kW-mo/yr
|
- | - | - | |
06 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $13,000 | $2,451 |
$12,355
148,856
kWh
|
$645
-
kW-mo/yr
|
- | - | - | |
07 | 2.7111: Reduce illumination to minimum necessary levels | $5,539 | $852 |
$5,179
62,400
kWh
|
$360
-
kW-mo/yr
|
- | - | - | |
08 | 2.7496: Install partitions to reduce size of conditioned space | $405 | $100 |
$387
4,666
kWh
|
$18
-
kW-mo/yr
|
- | - | - | |
09 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $681 | $1,206 |
$265
3,188
kWh
|
$12
-
kW-mo/yr
|
- | - | $404 | |
10 | 2.7243: Improve air circulation with destratification fans / other methods | $1,100 | $3,356 |
$(-382.0)
(-4,608)
kWh
|
$(-18.0)
-
kW-mo/yr
|
- |
$1,500
-
MMBtu
|
- | |
11 | 2.6211: Conserve energy by efficient use of vending machines | $641 | $1,206 |
$611
7,358
kWh
|
$30
-
kW-mo/yr
|
- | - | - | |
12 | 2.7135: Install occupancy sensors | $157 | $685 |
$157
1,888
kWh
|
- | - | - | - | |
13 | 4.652: Replace existing equipment with more suitable substitutes | $52,071 | $270,000 |
$48,685
586,560
kWh
|
$3,386
-
kW-mo/yr
|
- | - | - | |
14 | 2.3212: Optimize plant power factor | $3,069 | $20,067 | - | - | $3,069 | - | - | |
TOTAL RECOMMENDED | $127,989 | $300,964 |
$102,335
1,232,932
kWh
|
$9,191
-
kW-mo/yr
|
$3,069 |
$12,990
-
MMBtu
|
$404 | ||
TOTAL IMPLEMENTED | $56,169 | $4,737 |
$50,179
604,558
kWh
|
$5,586
-
kW-mo/yr
|
- | - | $404 | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Natural Gas Savings | One-time Revenue or Avoided Cost Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs