Assessment Year 2006
Principal Product Books
NAICS 323111: Commercial Printing (except Screen and Books)
SIC 2732: Book Printing
Sales Range $10
M
to 50
M
# of Employees 414
Plant Area 291,000
ft2
Annual Production 26,000,000
units
Production Hrs. Annual 6,240
hrs
Location (State) New York

Facility Energy Cost and Usage

Source Yearly Cost Usage
Electricity Usage $808,975 9,755,345
kWh
Electricity Demand $61,783 20,579
kW-mo/yr
Electricity Fees $3,981 -
Natural Gas $250,734 23,746
MMBtu
TOTAL YEARLY COSTS -
RECOMMENDED SAVINGS* $127,989 *Non-energy impacts included in savings.
IMPLEMENTED SAVINGS* $56,169

Recommendations

# Description Yearly Savings* Imp'd Cost* Status Electricity Usage Savings Electricity Demand Savings Electricity Fees Savings Natural Gas Savings One-time Revenue or Avoided Cost Savings
01 2.6218: Turn off equipment when not in use $25,842 - $21,807
262,734
kWh
$4,035
-
kW-mo/yr
- - -
02 2.4111: Utilize energy-efficient belts and other improved mechanisms $2,166 - $2,025
24,398
kWh
$141
-
kW-mo/yr
- - -
03 2.4314: Use synthetic lubricant $721 - $673
8,112
kWh
$48
-
kW-mo/yr
- - -
04 2.2437: Recover waste heat from equipment $11,490 $813 - - - $11,490
-
MMBtu
-
05 2.4221: Install compressor air intakes in coolest locations $11,107 $228 $10,573
127,380
kWh
$534
-
kW-mo/yr
- - -
06 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves $13,000 $2,451 $12,355
148,856
kWh
$645
-
kW-mo/yr
- - -
07 2.7111: Reduce illumination to minimum necessary levels $5,539 $852 $5,179
62,400
kWh
$360
-
kW-mo/yr
- - -
08 2.7496: Install partitions to reduce size of conditioned space $405 $100 $387
4,666
kWh
$18
-
kW-mo/yr
- - -
09 2.7142: Utilize higher efficiency lamps and/or ballasts $681 $1,206 $265
3,188
kWh
$12
-
kW-mo/yr
- - $404
10 2.7243: Improve air circulation with destratification fans / other methods $1,100 $3,356 $(-382.0)
(-4,608)
kWh
$(-18.0)
-
kW-mo/yr
- $1,500
-
MMBtu
-
11 2.6211: Conserve energy by efficient use of vending machines $641 $1,206 $611
7,358
kWh
$30
-
kW-mo/yr
- - -
12 2.7135: Install occupancy sensors $157 $685 $157
1,888
kWh
- - - -
13 4.652: Replace existing equipment with more suitable substitutes $52,071 $270,000 $48,685
586,560
kWh
$3,386
-
kW-mo/yr
- - -
14 2.3212: Optimize plant power factor $3,069 $20,067 - - $3,069 - -
TOTAL RECOMMENDED $127,989 $300,964 $102,335
1,232,932
kWh
$9,191
-
kW-mo/yr
$3,069 $12,990
-
MMBtu
$404
TOTAL IMPLEMENTED $56,169 $4,737 $50,179
604,558
kWh
$5,586
-
kW-mo/yr
- - $404
Yearly Savings* Imp'd Cost* Electricity Usage Savings Electricity Demand Savings Electricity Fees Savings Natural Gas Savings One-time Revenue or Avoided Cost Savings
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs