| Assessment Year | 2010 |
|---|---|
| Principal Product | Saw blades and packaged tool accessories |
| NAICS | 332216: Saw Blade and Handtool Manufacturing |
| SIC | 3425: Saw Blades and Handsaws |
| Sales Range | $50 M to 100M |
| # of Employees | 200 |
| Plant Area |
230,000
ft2
|
| Annual Production | 6,000,000
pieces
|
| Production Hrs. Annual | 6,000
hrs
|
| Location (State) | North Carolina |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $262,278 | 3,431,250 |
kWh
|
$0.076 |
| Electricity Demand | $31,838 | 8,420 |
kW-mo/yr
|
$3.78 |
| Electricity Fees | $4,586 | - |
|
- |
| Natural Gas | $30,273 | 2,273 |
MMBtu
|
$13.32 |
| TOTAL YEARLY COSTS | - | |||
| RECOMMENDED SAVINGS* | $31,648 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | $31,648 | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Personnel Changes Savings | Ancillary Material Cost Savings |
|---|---|---|---|---|---|---|---|---|---|
| 01 | 2.7228: Avoid introducing hot, humid, or dirty air into hvac system | $4,744 | $3,600 |
$1,473
19,901
kWh
|
$301
-
kW-mo/yr
|
$2,970
-
MMBtu
|
- | - | |
| 02 | 2.7241: Install outside air damper / economizer on hvac unit | $7,833 | - |
$7,112
96,140
kWh
|
$53
-
kW-mo/yr
|
- | - | $668 | |
| 03 | 2.7425: Clean or color roof to reduce solar load | $5,578 | - |
$4,514
61,021
kWh
|
$877
-
kW-mo/yr
|
- | - | $187 | |
| 04 | 2.6218: Turn off equipment when not in use | $1,940 | $7,800 |
$2,538
34,313
kWh
|
$302
-
kW-mo/yr
|
- | - | $(-900.0) | |
| 05 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $845 | $200 |
$1,656
22,380
kWh
|
$169
-
kW-mo/yr
|
- | $(-800.0) | $(-180.0) | |
| 06 | 2.2437: Recover waste heat from equipment | $4,947 | $6,200 | - | - |
$4,947
-
MMBtu
|
- | - | |
| 07 | 2.7135: Install occupancy sensors | $5,761 | $3,750 |
$7,151
96,660
kWh
|
- | - | - | $(-1,390.0) | |
| TOTAL RECOMMENDED | $31,648 | $21,550 |
$24,444
330,415
kWh
|
$1,702
-
kW-mo/yr
|
$7,917
-
MMBtu
|
$(-800.0) | $(-1,615.0) | ||
| TOTAL IMPLEMENTED | $31,648 | $21,550 |
$24,444
330,415
kWh
|
$1,702
-
kW-mo/yr
|
$7,917
-
MMBtu
|
$(-800.0) | $(-1,615.0) | ||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Personnel Changes Savings | Ancillary Material Cost Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs