ITAC Assessment: SU0227
ITAC logo
ITAC Assessment: SU0227
Grant Funding Opportunity NOW OPEN
Up to $300k at 50% cost share for qualifying* projects.
Grant Funding Opportunity Open
Qualifying* small and medium-sized US manufacturers, that received an ITAC, Onsite Energy/CHP TAP, or qualified equivalent assessment since 2018 can now apply for grants for implementation of assessment recommendations at up to 50% of qualifying* project costs with a maximum of $300,000 per grant.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
Assessment Year 2005
Principal Product Wine
NAICS 312130: Wineries
SIC 2084: Wines, Brandy, and Brandy Spirits
Sales Range $10
M
to 50
M
# of Employees 100
Plant Area 272,500
ft2
Annual Production 3,000,000
pieces
Production Hrs. Annual 3,060
hrs
Location (State) New York

Facility Energy Cost and Usage

Source Yearly Cost Usage
Electricity Usage $332,264 4,301,850
kWh
Electricity Demand $50,380 13,235
kW-mo/yr
Electricity Fees $7,027 -
Natural Gas $278,244 26,228
MMBtu
TOTAL YEARLY COSTS -
RECOMMENDED SAVINGS* $34,828 *Non-energy impacts included in savings.
IMPLEMENTED SAVINGS* $1,879

Recommendations

# Description Yearly Savings* Imp'd Cost* Status Electricity Usage Savings Electricity Demand Savings Electricity Fees Savings Natural Gas Savings One-time Revenue or Avoided Cost Savings
01 2.4231: Reduce the pressure of compressed air to the minimum required $1,070 - $839
10,487
kWh
$231
-
kW-mo/yr
- - -
02 2.4111: Utilize energy-efficient belts and other improved mechanisms $434 - $359
4,488
kWh
$75
-
kW-mo/yr
- - -
03 2.8114: Change rate schedules or other changes in utility service $209 - - - - - $209
04 2.2414: Use waste heat from hot flue gases to preheat $13,581 $2,035 - - - $13,581
-
MMBtu
-
05 2.7111: Reduce illumination to minimum necessary levels $11,968 $1,970 $8,585
136,274
kWh
$3,383
-
kW-mo/yr
- - -
06 2.4221: Install compressor air intakes in coolest locations $1,737 $496 $1,515
18,941
kWh
$222
-
kW-mo/yr
- - -
07 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves $629 $228 $548
6,854
kWh
$81
-
kW-mo/yr
- - -
08 2.1231: Establish burner maintenance schedule for boilers $2,257 $1,220 - - - - $2,257
09 2.7142: Utilize higher efficiency lamps and/or ballasts $725 $1,187 $410
5,500
kWh
$34
-
kW-mo/yr
- - $281
10 2.6211: Conserve energy by efficient use of vending machines $607 $1,187 $571
7,358
kWh
$36
-
kW-mo/yr
- - -
11 2.7135: Install occupancy sensors $91 $194 $91
1,139
kWh
- - - -
12 2.3212: Optimize plant power factor $1,520 $13,971 - - $1,520 - -
TOTAL RECOMMENDED $34,828 $22,488 $12,918
191,041
kWh
$4,062
-
kW-mo/yr
$1,520 $13,581
-
MMBtu
$2,747
TOTAL IMPLEMENTED $1,879 $1,609 $1,408
17,981
kWh
$190
-
kW-mo/yr
- - $281
Yearly Savings* Imp'd Cost* Electricity Usage Savings Electricity Demand Savings Electricity Fees Savings Natural Gas Savings One-time Revenue or Avoided Cost Savings
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs