Assessment Year 2005
Principal Product Ceramic Capacitors
NAICS 334416: Capacitor, Resistor, Coil, Transformer, and Other Inductor Manufacturing
SIC 3675: Electronic Capacitors
Sales Range $50
M
to 100
M
# of Employees 160
Plant Area 121,200
ft2
Annual Production 51,000,000
pieces
Production Hrs. Annual 8,760
hrs
Location (State) New York

Facility Energy Cost and Usage

Source Yearly Cost Usage
Electricity Usage $230,991 3,903,703
kWh
Electricity Demand $160,373 7,145
kW-mo/yr
Electricity Fees $7,285 -
Natural Gas $141,578 16,189
MMBtu
TOTAL YEARLY COSTS -
RECOMMENDED SAVINGS* $154,315 *Non-energy impacts included in savings.
IMPLEMENTED SAVINGS* $47,585

Recommendations

# Description Yearly Savings* Imp'd Cost* Status Electricity Usage Savings Electricity Demand Savings One-time Revenue or Avoided Cost Savings
01 2.8114: Change rate schedules or other changes in utility service $15,621 - - - $15,621
02 2.4231: Reduce the pressure of compressed air to the minimum required $7,400 - $3,628
61,496
kWh
$3,772
-
kW-mo/yr
-
03 2.4111: Utilize energy-efficient belts and other improved mechanisms $2,356 - $1,279
21,680
kWh
$1,077
-
kW-mo/yr
-
04 2.4221: Install compressor air intakes in coolest locations $15,286 $502 $7,473
126,670
kWh
$7,813
-
kW-mo/yr
-
05 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves $3,948 $721 $1,927
32,675
kWh
$2,021
-
kW-mo/yr
-
06 2.4146: Use adjustable frequency drive or multiple speed motors on existing system $40,969 $38,400 $22,336
378,593
kWh
$18,633
-
kW-mo/yr
-
07 2.7122: Disconnect ballasts $6,107 $5,363 $4,019
68,118
kWh
$2,088
-
kW-mo/yr
-
08 2.7135: Install occupancy sensors $1,137 $1,726 $1,137
19,272
kWh
- -
09 2.7142: Utilize higher efficiency lamps and/or ballasts $694 $1,262 $233
3,942
kWh
$112
-
kW-mo/yr
$349
10 2.6211: Conserve energy by efficient use of vending machines $276 $509 $186
3,150
kWh
$90
-
kW-mo/yr
-
11 3.1191: Change procedures / equipment / operating conditions $53,360 $111,859 - - $53,360
12 2.7131: Add area lighting switches $4,267 $10,645 $4,267
72,331
kWh
- -
13 2.3212: Optimize plant power factor $2,894 $17,500 - - $2,894
TOTAL RECOMMENDED $154,315 $188,487 $46,485
787,927
kWh
$35,606
-
kW-mo/yr
$72,224
TOTAL IMPLEMENTED $47,585 $17,231 $18,965
321,474
kWh
$12,999
-
kW-mo/yr
$15,621
Yearly Savings* Imp'd Cost* Electricity Usage Savings Electricity Demand Savings One-time Revenue or Avoided Cost Savings
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs