Assessment Year | 2005 |
---|---|
Principal Product | Ceramic Capacitors |
NAICS | 334416: Capacitor, Resistor, Coil, Transformer, and Other Inductor Manufacturing |
SIC | 3675: Electronic Capacitors |
Sales Range | $50 M to 100M |
# of Employees | 160 |
Plant Area |
121,200
ft2
|
Annual Production | 51,000,000
pieces
|
Production Hrs. Annual | 8,760
hrs
|
Location (State) | New York |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $230,991 | 3,903,703 |
kWh
|
$0.059 |
Electricity Demand | $160,373 | 7,145 |
kW-mo/yr
|
$22.45 |
Electricity Fees | $7,285 | - |
|
- |
Natural Gas | $141,578 | 16,189 |
MMBtu
|
$8.75 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $154,315 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $47,585 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | One-time Revenue or Avoided Cost Savings |
---|---|---|---|---|---|---|---|
01 | 2.8114: Change rate schedules or other changes in utility service | $15,621 | - | - | - | $15,621 | |
02 | 2.4231: Reduce the pressure of compressed air to the minimum required | $7,400 | - |
$3,628
61,496
kWh
|
$3,772
-
kW-mo/yr
|
- | |
03 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $2,356 | - |
$1,279
21,680
kWh
|
$1,077
-
kW-mo/yr
|
- | |
04 | 2.4221: Install compressor air intakes in coolest locations | $15,286 | $502 |
$7,473
126,670
kWh
|
$7,813
-
kW-mo/yr
|
- | |
05 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $3,948 | $721 |
$1,927
32,675
kWh
|
$2,021
-
kW-mo/yr
|
- | |
06 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $40,969 | $38,400 |
$22,336
378,593
kWh
|
$18,633
-
kW-mo/yr
|
- | |
07 | 2.7122: Disconnect ballasts | $6,107 | $5,363 |
$4,019
68,118
kWh
|
$2,088
-
kW-mo/yr
|
- | |
08 | 2.7135: Install occupancy sensors | $1,137 | $1,726 |
$1,137
19,272
kWh
|
- | - | |
09 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $694 | $1,262 |
$233
3,942
kWh
|
$112
-
kW-mo/yr
|
$349 | |
10 | 2.6211: Conserve energy by efficient use of vending machines | $276 | $509 |
$186
3,150
kWh
|
$90
-
kW-mo/yr
|
- | |
11 | 3.1191: Change procedures / equipment / operating conditions | $53,360 | $111,859 | - | - | $53,360 | |
12 | 2.7131: Add area lighting switches | $4,267 | $10,645 |
$4,267
72,331
kWh
|
- | - | |
13 | 2.3212: Optimize plant power factor | $2,894 | $17,500 | - | - | $2,894 | |
TOTAL RECOMMENDED | $154,315 | $188,487 |
$46,485
787,927
kWh
|
$35,606
-
kW-mo/yr
|
$72,224 | ||
TOTAL IMPLEMENTED | $47,585 | $17,231 |
$18,965
321,474
kWh
|
$12,999
-
kW-mo/yr
|
$15,621 | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | One-time Revenue or Avoided Cost Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs