Assessment Year | 2005 |
---|---|
Principal Product | Thick Film Micro-Electronic Components |
NAICS | 334418: Printed Circuit Assembly (Electronic Assembly) Manufacturing |
SIC | 3679: Electronic Components, Not Elsewhere Classified |
Sales Range | $10 M to 50M |
# of Employees | 127 |
Plant Area |
45,000
ft2
|
Annual Production | 91,322
pieces
|
Production Hrs. Annual | 4,284
hrs
|
Location (State) | New York |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $173,621 | 2,023,504 |
kWh
|
$0.086 |
Electricity Demand | $53,139 | 3,904 |
kW-mo/yr
|
$13.61 |
Electricity Fees | $3,175 | - |
|
- |
Natural Gas | $36,676 | 3,834 |
MMBtu
|
$9.57 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $145,934 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $9,200 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | One-time Revenue or Avoided Cost Savings |
---|---|---|---|---|---|---|---|---|
01 | 4.821: Pay bills on time to avoid late fees | $395 | - | - | - | - | $395 | |
02 | 2.4231: Reduce the pressure of compressed air to the minimum required | $3,679 | - |
$3,012
33,466
kWh
|
$667
-
kW-mo/yr
|
- | - | |
03 | 2.4314: Use synthetic lubricant | $375 | - |
$307
3,407
kWh
|
$68
-
kW-mo/yr
|
- | - | |
04 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $670 | - |
$547
6,079
kWh
|
$123
-
kW-mo/yr
|
- | - | |
05 | 2.1222: Install turbulators | $985 | $571 | - | - |
$985
-
MMBtu
|
- | |
06 | 2.4221: Install compressor air intakes in coolest locations | $2,637 | $1,889 |
$2,147
23,856
kWh
|
$490
-
kW-mo/yr
|
- | - | |
07 | 2.2492: Use "heat wheel" or other heat exchanger to cross-exchange building exhaust air with make-up air | $12,179 | $10,575 | - | - |
$12,179
-
MMBtu
|
- | |
08 | 2.7135: Install occupancy sensors | $1,966 | $2,792 |
$1,966
21,840
kWh
|
- | - | - | |
09 | 2.6211: Conserve energy by efficient use of vending machines | $230 | $383 |
$189
2,097
kWh
|
$41
-
kW-mo/yr
|
- | - | |
10 | 2.7124: Make a practice of turning off lights when not needed | $148 | $527 |
$148
1,643
kWh
|
- | - | - | |
11 | 2.7314: Reduce ventilation air | $3,820 | $13,919 |
$3,738
41,539
kWh
|
$82
-
kW-mo/yr
|
- | - | |
12 | 2.1311: Replace electrically-operated equipment with fossil fuel equipment | $97,661 | $114,600 |
$60,934
677,040
kWh
|
$12,657
-
kW-mo/yr
|
$34,903
-
MMBtu
|
$(-10,833.0) | |
13 | 3.1191: Change procedures / equipment / operating conditions | $21,189 | $111,859 | - | - | - | $21,189 | |
TOTAL RECOMMENDED | $145,934 | $257,115 |
$72,988
810,967
kWh
|
$14,128
-
kW-mo/yr
|
$48,067
-
MMBtu
|
$10,751 | ||
TOTAL IMPLEMENTED | $9,200 | $5,208 |
$7,580
84,212
kWh
|
$1,225
-
kW-mo/yr
|
- | $395 | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | One-time Revenue or Avoided Cost Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs