Assessment Year | 2005 |
---|---|
Principal Product | Garden Sprayers |
NAICS | 326191: Plastics Plumbing Fixture Manufacturing |
SIC | 3524: Lawn and Garden Tractors and Home Lawn and Garden Equipment |
Sales Range | $10 M to 50M |
# of Employees | 200 |
Plant Area |
160,000
ft2
|
Annual Production | 2,000,000
pieces
|
Production Hrs. Annual | 7,344
hrs
|
Location (State) | New York |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $145,314 | 4,297,127 |
kWh
|
$0.034 |
Electricity Demand | $142,980 | 9,349 |
kW-mo/yr
|
$15.29 |
Electricity Fees | $12,573 | - |
|
- |
Natural Gas | $33,859 | 3,596 |
MMBtu
|
$9.42 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $14,384 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $3,320 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | One-time Revenue or Avoided Cost Savings |
---|---|---|---|---|---|---|---|---|
01 | 2.4231: Reduce the pressure of compressed air to the minimum required | $3,324 | - |
$1,918
56,402
kWh
|
$1,406
-
kW-mo/yr
|
- | - | |
02 | 2.7124: Make a practice of turning off lights when not needed | $938 | - |
$938
27,594
kWh
|
- | - | - | |
03 | 2.8114: Change rate schedules or other changes in utility service | $677 | - | - | - | - | $677 | |
04 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $175 | - |
$99
2,901
kWh
|
$76
-
kW-mo/yr
|
- | - | |
05 | 2.4221: Install compressor air intakes in coolest locations | $1,158 | $344 |
$669
19,682
kWh
|
$489
-
kW-mo/yr
|
- | - | |
06 | 2.7124: Make a practice of turning off lights when not needed | $1,236 | $748 |
$671
19,728
kWh
|
$565
-
kW-mo/yr
|
- | - | |
07 | 2.4314: Use synthetic lubricant | $3,145 | $2,000 |
$1,815
53,391
kWh
|
$1,330
-
kW-mo/yr
|
- | - | |
08 | 2.3212: Optimize plant power factor | $3,731 | $11,931 | - | - | $3,731 | - | |
TOTAL RECOMMENDED | $14,384 | $15,023 |
$6,110
179,698
kWh
|
$3,866
-
kW-mo/yr
|
$3,731 | $677 | ||
TOTAL IMPLEMENTED | $3,320 | $2,000 |
$1,914
56,292
kWh
|
$1,406
-
kW-mo/yr
|
- | - | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | One-time Revenue or Avoided Cost Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs