| Assessment Year | 2003 | 
|---|---|
| Principal Product | Green Lumber | 
| NAICS | 321912: Cut Stock, Resawing Lumber, and Planing | 
| SIC | 2421: Sawmills and Planing Mills, General | 
| Sales Range | $1 M  to 5M  | 
    
| # of Employees | 60 | 
| Plant Area | 
                            37,000
                 
ft2
 
                     | 
    
| Annual Production | 8,000
             
thousand feet
 
         | 
    
| Production Hrs. Annual | 2,410
             
hrs
 
         | 
    
| Location (State) | Kentucky | 
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $108,517 | 1,647,847 | 
             
kWh
 
         | 
        $0.066 | 
| Electricity Demand | $44,300 | 7,308 | 
             
kW-mo/yr
 
         | 
        $6.06 | 
| TOTAL YEARLY COSTS | - | |||
| RECOMMENDED SAVINGS* | $18,506 | 
             See individual recommendations below 
            *Non-energy impacts included in savings.
         | 
    ||
| IMPLEMENTED SAVINGS* | $16,500 | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | 
|---|---|---|---|---|---|---|
| 01 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $207 | - | 
                        $102
                                                     1,738
                                 
                                            
kWh
 
                             | 
                                                                                
                        $105
                                                     -
                                 
                                            
kW-mo/yr
 
                             | 
                                    |
| 02 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $801 | $2,160 | 
                        $504
                                                     12,934
                                 
                                            
kWh
 
                             | 
                                                                                
                        $297
                                                     -
                                 
                                            
kW-mo/yr
 
                             | 
                                    |
| 03 | 2.6221: Use most efficient equipment at it's maximum capacity and less efficient equipment only when necessary | $7,007 | $915 | 
                        $3,953
                                                     101,378
                                 
                                            
kWh
 
                             | 
                                                                                
                        $3,054
                                                     -
                                 
                                            
kW-mo/yr
 
                             | 
                                    |
| 04 | 2.4231: Reduce the pressure of compressed air to the minimum required | $1,172 | $30 | 
                        $663
                                                     17,009
                                 
                                            
kWh
 
                             | 
                                                                                
                        $509
                                                     -
                                 
                                            
kW-mo/yr
 
                             | 
                                    |
| 05 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $6,218 | $2,025 | 
                        $3,506
                                                     89,951
                                 
                                            
kWh
 
                             | 
                                                                                
                        $2,712
                                                     -
                                 
                                            
kW-mo/yr
 
                             | 
                                    |
| 06 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $1,095 | $250 | 
                        $617
                                                     15,857
                                 
                                            
kWh
 
                             | 
                                                                                
                        $478
                                                     -
                                 
                                            
kW-mo/yr
 
                             | 
                                    |
| 07 | 2.4221: Install compressor air intakes in coolest locations | $406 | $405 | 
                        $228
                                                     5,900
                                 
                                            
kWh
 
                             | 
                                                                                
                        $178
                                                     -
                                 
                                            
kW-mo/yr
 
                             | 
                                    |
| 08 | 2.4239: Eliminate or reduce compressed air usage | $1,600 | $40 | 
                        $902
                                                     23,134
                                 
                                            
kWh
 
                             | 
                                                                                
                        $698
                                                     -
                                 
                                            
kW-mo/yr
 
                             | 
                                    |
| TOTAL RECOMMENDED | $18,506 | $5,825 | 
                        $10,475
                                                     267,901
                                 
                                            
kWh
 
                             | 
                                                                                
                        $8,031
                                                     -
                                 
                                            
kW-mo/yr
 
                             | 
                                    ||
| TOTAL IMPLEMENTED | $16,500 | $5,380 | 
                        $9,345
                                                     238,867
                                 
                                            
kWh
 
                             | 
                                                                                
                        $7,155
                                                     -
                                 
                                            
kW-mo/yr
 
                             | 
                                    ||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs