Assessment Year 2003
Principal Product Green Lumber
NAICS 321912: Cut Stock, Resawing Lumber, and Planing
SIC 2421: Sawmills and Planing Mills, General
Sales Range $1
M
to 5
M
# of Employees 60
Plant Area 37,000
ft2
Annual Production 8,000
thousand feet
Production Hrs. Annual 2,410
hrs
Location (State) Kentucky

Facility Energy Cost and Usage

Source Yearly Cost Usage
Electricity Usage $108,517 1,647,847
kWh
Electricity Demand $44,300 7,308
kW-mo/yr
TOTAL YEARLY COSTS -
RECOMMENDED SAVINGS* $18,506 *Non-energy impacts included in savings.
IMPLEMENTED SAVINGS* $16,500

Recommendations

# Description Yearly Savings* Imp'd Cost* Status Electricity Usage Savings Electricity Demand Savings
01 2.7142: Utilize higher efficiency lamps and/or ballasts $207 - $102
1,738
kWh
$105
-
kW-mo/yr
02 2.7142: Utilize higher efficiency lamps and/or ballasts $801 $2,160 $504
12,934
kWh
$297
-
kW-mo/yr
03 2.6221: Use most efficient equipment at it's maximum capacity and less efficient equipment only when necessary $7,007 $915 $3,953
101,378
kWh
$3,054
-
kW-mo/yr
04 2.4231: Reduce the pressure of compressed air to the minimum required $1,172 $30 $663
17,009
kWh
$509
-
kW-mo/yr
05 2.4111: Utilize energy-efficient belts and other improved mechanisms $6,218 $2,025 $3,506
89,951
kWh
$2,712
-
kW-mo/yr
06 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves $1,095 $250 $617
15,857
kWh
$478
-
kW-mo/yr
07 2.4221: Install compressor air intakes in coolest locations $406 $405 $228
5,900
kWh
$178
-
kW-mo/yr
08 2.4239: Eliminate or reduce compressed air usage $1,600 $40 $902
23,134
kWh
$698
-
kW-mo/yr
TOTAL RECOMMENDED $18,506 $5,825 $10,475
267,901
kWh
$8,031
-
kW-mo/yr
TOTAL IMPLEMENTED $16,500 $5,380 $9,345
238,867
kWh
$7,155
-
kW-mo/yr
Yearly Savings* Imp'd Cost* Electricity Usage Savings Electricity Demand Savings