Assessment Year | 2004 |
---|---|
Principal Product | Newspapers |
NAICS | 511110: Newspaper Publishers |
SIC | 2752: Commercial Printing, Lithographic |
Sales Range | $5 M to 10M |
# of Employees | 247 |
Plant Area |
76,052
ft2
|
Annual Production | 15,000,000
pieces
|
Production Hrs. Annual | 4,732
hrs
|
Location (State) | New York |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $121,730 | 1,484,700 |
kWh
|
$0.082 |
Electricity Demand | $70,733 | 4,725 |
kW-mo/yr
|
$14.97 |
Natural Gas | $52,842 | 7,371 |
MMBtu
|
$7.17 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $42,563 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $34,851 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Personnel Changes Savings | One-time Revenue or Avoided Cost Savings |
---|---|---|---|---|---|---|---|---|---|
01 | 2.6218: Turn off equipment when not in use | $12,704 | - |
$9,066
110,565
kWh
|
$3,638
-
kW-mo/yr
|
- | - | - | |
02 | 2.8114: Change rate schedules or other changes in utility service | $5,982 | - | - | - | - | - | $5,982 | |
03 | 2.4226: Use / purchase optimum sized compressor | $16,485 | $1,693 |
$7,869
95,964
kWh
|
$2,216
-
kW-mo/yr
|
- | - | $6,400 | |
04 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $2,635 | $400 |
$1,479
18,043
kWh
|
$689
-
kW-mo/yr
|
- | $390 | $77 | |
05 | 2.4221: Install compressor air intakes in coolest locations | $938 | $298 |
$788
9,620
kWh
|
$150
-
kW-mo/yr
|
- | - | - | |
06 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $792 | $461 |
$116
1,411
kWh
|
$30
-
kW-mo/yr
|
- | $540 | $106 | |
07 | 2.2511: Insulate bare equipment | $236 | $154 | - | - |
$236
-
MMBtu
|
- | - | |
08 | 2.4314: Use synthetic lubricant | $1,467 | $1,000 |
$1,467
17,887
kWh
|
- | - | - | - | |
09 | 2.4239: Eliminate or reduce compressed air usage | $1,324 | $1,305 |
$830
10,127
kWh
|
$494
-
kW-mo/yr
|
- | - | - | |
TOTAL RECOMMENDED | $42,563 | $5,311 |
$21,615
263,617
kWh
|
$7,217
-
kW-mo/yr
|
$236
-
MMBtu
|
$930 | $12,565 | ||
TOTAL IMPLEMENTED | $34,851 | $4,552 |
$20,711
252,586
kWh
|
$7,037
-
kW-mo/yr
|
$236
-
MMBtu
|
$390 | $6,477 | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Personnel Changes Savings | One-time Revenue or Avoided Cost Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs