Assessment Year | 2003 |
---|---|
Principal Product | Nutritional/Diet Bars |
NAICS | 311352: Confectionery Manufacturing from Purchased Chocolate |
SIC | 2064: Candy and Other Confectionery Products |
Sales Range | $10 M to 50M |
# of Employees | 78 |
Plant Area |
61,600
ft2
|
Annual Production | 70,000,000
pieces
|
Production Hrs. Annual | 2,080
hrs
|
Location (State) | New York |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $89,850 | 1,512,900 |
kWh
|
$0.059 |
Electricity Demand | $37,863 | 3,606 |
kW-mo/yr
|
$10.50 |
Electricity Fees | $16,968 | - |
|
- |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $37,256 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $5,920 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Administrative Changes Savings |
---|---|---|---|---|---|---|---|---|
01 | 2.3134: Shift from daytime to nighttime operation | $13,244 | - | - | - | - | $13,244 | |
02 | 2.4231: Reduce the pressure of compressed air to the minimum required | $3,991 | - |
$2,882
41,170
kWh
|
$1,109
-
kW-mo/yr
|
- | - | |
03 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $919 | $57 |
$756
10,800
kWh
|
$163
-
kW-mo/yr
|
- | - | |
04 | 2.4221: Install compressor air intakes in coolest locations | $1,102 | $117 |
$797
11,384
kWh
|
$305
-
kW-mo/yr
|
- | - | |
05 | 2.4239: Eliminate or reduce compressed air usage | $3,444 | $4,290 |
$1,846
26,374
kWh
|
$1,598
-
kW-mo/yr
|
- | - | |
06 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $5,001 | $9,164 |
$3,171
45,302
kWh
|
$1,830
-
kW-mo/yr
|
- | - | |
07 | 2.7232: Replace existing hvac unit with high efficiency model | $9,555 | $48,418 |
$2,869
40,988
kWh
|
$3,311
-
kW-mo/yr
|
$3,375 | - | |
TOTAL RECOMMENDED | $37,256 | $62,046 |
$12,321
176,018
kWh
|
$8,316
-
kW-mo/yr
|
$3,375 | $13,244 | ||
TOTAL IMPLEMENTED | $5,920 | $9,221 |
$3,927
56,102
kWh
|
$1,993
-
kW-mo/yr
|
- | - | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Administrative Changes Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs