Assessment Year | 2003 |
---|---|
Principal Product | Electrical Insulating Sleeves |
NAICS | 325211: Plastics Material and Resin Manufacturing |
SIC | 3699: Electrical Machinery, Equipment, and Supplies, Not Elsewhere |
Sales Range | $5 M to 10M |
# of Employees | 90 |
Plant Area |
140,000
ft2
|
Annual Production | 1,000
thousand feet
|
Production Hrs. Annual | 6,000
hrs
|
Location (State) | New York |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $114,674 | 1,758,883 |
kWh
|
$0.065 |
Electricity Demand | $68,979 | 5,580 |
kW-mo/yr
|
$12.36 |
Electricity Fees | $13,648 | - |
|
- |
Natural Gas | $17,067 | 5,951 |
MMBtu
|
$2.87 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $16,254 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $4,810 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings |
---|---|---|---|---|---|---|---|
01 | 2.2492: Use "heat wheel" or other heat exchanger to cross-exchange building exhaust air with make-up air | $5,869 | $18,122 | - | - |
$5,869
-
MMBtu
|
|
02 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $5,575 | $15,750 |
$4,120
58,860
kWh
|
$1,455
-
kW-mo/yr
|
- | |
03 | 2.4314: Use synthetic lubricant | $1,187 | $800 |
$877
12,527
kWh
|
$310
-
kW-mo/yr
|
- | |
04 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $1,171 | - |
$865
12,360
kWh
|
$306
-
kW-mo/yr
|
- | |
05 | 2.1224: Replace boiler | $1,148 | $13,507 | - | - |
$1,148
-
MMBtu
|
|
06 | 2.4231: Reduce the pressure of compressed air to the minimum required | $1,028 | - |
$760
10,859
kWh
|
$268
-
kW-mo/yr
|
- | |
07 | 2.4221: Install compressor air intakes in coolest locations | $276 | $523 |
$202
2,891
kWh
|
$74
-
kW-mo/yr
|
- | |
TOTAL RECOMMENDED | $16,254 | $48,702 |
$6,824
97,497
kWh
|
$2,413
-
kW-mo/yr
|
$7,017
-
MMBtu
|
||
TOTAL IMPLEMENTED | $4,810 | $14,830 |
$2,704
38,637
kWh
|
$958
-
kW-mo/yr
|
$1,148
-
MMBtu
|
||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs