Assessment Year | 2003 |
---|---|
Principal Product | Contract Packaging, Warehousing |
NAICS | 488991: Packing and Crating |
SIC | 4783: Packing and Crating |
Sales Range | $10 M to 50M |
# of Employees | 300 |
Plant Area |
152,000
ft2
|
Annual Production | 0
units
|
Production Hrs. Annual | 4,375
hrs
|
Location (State) | New York |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $82,515 | 1,533,022 |
kWh
|
$0.054 |
Electricity Demand | $23,177 | 4,508 |
kW-mo/yr
|
$5.14 |
Electricity Fees | $8,799 | - |
|
- |
Natural Gas | $58,667 | 10,006 |
MMBtu
|
$5.86 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $66,225 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $3,358 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings |
---|---|---|---|---|---|---|---|
01 | 2.6218: Turn off equipment when not in use | $45,993 | - |
$39,475
664,518
kWh
|
$6,518
-
kW-mo/yr
|
- | |
02 | 2.2414: Use waste heat from hot flue gases to preheat | $2,969 | $11,310 | - | - |
$2,969
-
MMBtu
|
|
03 | 2.2437: Recover waste heat from equipment | $7,728 | $2,468 | - | - |
$7,728
-
MMBtu
|
|
04 | 2.6218: Turn off equipment when not in use | $1,835 | - |
$1,495
23,100
kWh
|
$340
-
kW-mo/yr
|
- | |
05 | 2.2531: Re-size charging openings or add movable cover or door | $1,647 | $8,000 | - | - |
$1,647
-
MMBtu
|
|
06 | 2.7243: Improve air circulation with destratification fans / other methods | $2,020 | $7,486 | - | - |
$2,020
-
MMBtu
|
|
07 | 2.4231: Reduce the pressure of compressed air to the minimum required | $1,147 | - |
$1,147
22,940
kWh
|
- | - | |
08 | 2.6212: Turn off equipment during breaks, reduce operating time | $858 | - |
$858
17,160
kWh
|
- | - | |
09 | 2.7135: Install occupancy sensors | $849 | $640 |
$849
12,128
kWh
|
- | - | |
10 | 2.1233: Analyze flue gas for proper air/fuel ratio | $803 | $406 | - | - |
$803
-
MMBtu
|
|
11 | 2.4221: Install compressor air intakes in coolest locations | $376 | $558 |
$376
7,517
kWh
|
- | - | |
TOTAL RECOMMENDED | $66,225 | $30,868 |
$44,200
747,363
kWh
|
$6,858
-
kW-mo/yr
|
$15,167
-
MMBtu
|
||
TOTAL IMPLEMENTED | $3,358 | $558 |
$3,018
53,557
kWh
|
$340
-
kW-mo/yr
|
- | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs