Assessment Year | 2001 |
---|---|
Principal Product | brake pistons |
NAICS |
n/a
|
SIC | 3089: Plastics Products, Not Elsewhere Classified |
Sales Range | $10 M to 50M |
# of Employees | 100 |
Plant Area |
41,650
ft2
|
Annual Production | 16,000
pieces
|
Production Hrs. Annual | 5,760
hrs
|
Location (State) | New York |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $165,323 | 2,570,243 |
kWh
|
$0.064 |
Electricity Demand | $44,091 | 5,636 |
kW-mo/yr
|
$7.82 |
Electricity Fees | $6,385 | - |
|
- |
Natural Gas | $62,812 | 7,833 |
MMBtu
|
$8.02 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $78,883 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $63,651 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Natural Gas Savings | Ancillary Material Cost Savings | One-time Revenue or Avoided Cost Savings |
---|---|---|---|---|---|---|---|---|---|---|
01 | 2.8121: Apply for tax-free status for energy purchases | $1,561 | - | - | - | - | - | - | $1,561 | |
02 | 2.4231: Reduce the pressure of compressed air to the minimum required | $6,467 | - |
$6,467
107,784
kWh
|
- | - | - | - | - | |
03 | 2.4221: Install compressor air intakes in coolest locations | $6,122 | $20,070 |
$6,122
102,036
kWh
|
- | - | - | - | - | |
04 | 2.7135: Install occupancy sensors | $2,096 | $665 |
$1,698
28,309
kWh
|
$398
-
kW-mo/yr
|
- | - | - | - | |
05 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $1,687 | $342 |
$1,328
22,136
kWh
|
$359
-
kW-mo/yr
|
- | - | - | - | |
06 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $2,313 | $840 |
$1,819
30,319
kWh
|
$494
-
kW-mo/yr
|
- | - | - | - | |
07 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $920 | $3,275 |
$724
12,080
kWh
|
$196
-
kW-mo/yr
|
- | - | - | - | |
08 | 2.3212: Optimize plant power factor | $4,470 | $6,200 | - | - | $4,470 | - | - | - | |
09 | 3.4111: Use closed cycle process to minimize waste water production | $34,312 | - |
$29,030
483,840
kWh
|
$7,882
-
kW-mo/yr
|
- | - | $(-2,600.0) | - | |
10 | 3.6193: Install equipment (eg compactor) to reduce disposal costs | $8,216 | $9,990 | - | - | - |
$8,216
-
MMBtu
|
- | - | |
11 | 2.2437: Recover waste heat from equipment | $10,719 | $760 | - | - | - |
$10,719
-
MMBtu
|
- | - | |
TOTAL RECOMMENDED | $78,883 | $42,142 |
$47,188
786,504
kWh
|
$9,329
-
kW-mo/yr
|
$4,470 |
$18,935
-
MMBtu
|
$(-2,600.0) | $1,561 | ||
TOTAL IMPLEMENTED | $63,651 | $27,030 |
$41,619
693,660
kWh
|
$7,882
-
kW-mo/yr
|
$4,470 |
$10,719
-
MMBtu
|
$(-2,600.0) | $1,561 | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Natural Gas Savings | Ancillary Material Cost Savings | One-time Revenue or Avoided Cost Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs