| Assessment Year | 1985 |
|---|---|
| Principal Product | CUSTOMIZED STEEL DRUMS |
| NAICS |
n/a
|
| SIC | 3412: Metal Shipping Barrels, Drums, Kegs, and Pails |
| Sales Range | $10 M to 50M |
| # of Employees | 125 |
| Plant Area |
n/a
|
| Annual Production | 1,300,000
pieces
|
| Production Hrs. Annual | 4,250
hrs
|
| Location (State) | New Jersey |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $196,642 | 2,478,019 |
kWh
|
$0.079 |
| Natural Gas | $259,056 | 36,076 |
MMBtu
|
$7.18 |
| Fuel Oil #2 | $1,661 | 280 |
MMBtu
|
$5.93 |
| TOTAL YEARLY COSTS | - | |||
| RECOMMENDED SAVINGS* | $60,293 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | - | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Natural Gas Savings | Fuel Oil #2 Savings | Administrative Changes Savings |
|---|---|---|---|---|---|---|---|---|
| 01 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $16,975 | $500 |
$16,975
213,951
kWh
|
- | - | - | |
| 02 | 2.4312: Improve lubrication practices | $4,051 | - |
$4,231
53,341
kWh
|
- | - | $(-180.0) | |
| 03 | 2.4133: Use most efficient type of electric motors | $5,293 | $10,360 |
$5,293
66,823
kWh
|
- | - | - | |
| 04 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $651 | $1,550 |
$651
8,206
kWh
|
- | - | - | |
| 05 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $1,832 | $480 |
$1,832
23,154
kWh
|
- | - | - | |
| 06 | 2.4221: Install compressor air intakes in coolest locations | $651 | $250 |
$651
8,206
kWh
|
- | - | - | |
| 07 | 2.2437: Recover waste heat from equipment | $3,964 | $1,600 | - |
$3,964
-
MMBtu
|
- | - | |
| 08 | 2.7447: Install vinyl strip / high speed / air curtain doors | $4,632 | $545 | - |
$4,632
-
MMBtu
|
- | - | |
| 09 | 2.7229: Air condition only space necessary | $453 | $800 | - |
$453
-
MMBtu
|
- | - | |
| 10 | 2.7224: Reduce space conditioning during non-working hours | $15,049 | - | - |
$14,115
-
MMBtu
|
$934
-
MMBtu
|
- | |
| 11 | 2.1123: Install automatic stack damper | $961 | $4,950 | - |
$961
-
MMBtu
|
- | - | |
| 12 | 3.4115: Recover and reuse cooling water | $5,781 | - |
$59
879
kWh
|
- | - | $5,722 | |
| TOTAL RECOMMENDED | $60,293 | $21,035 |
$29,692
374,560
kWh
|
$24,125
-
MMBtu
|
$934
-
MMBtu
|
$5,542 | ||
| TOTAL IMPLEMENTED | - | - | - | - | - | - | ||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Natural Gas Savings | Fuel Oil #2 Savings | Administrative Changes Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs