Assessment Year | 1985 |
---|---|
Principal Product | INDUSTRIAL GLOVES |
NAICS |
n/a
|
SIC | 2381: Dress and Work Gloves, Except Knit and All-Leather |
Sales Range | $10 M to 50M |
# of Employees | 82 |
Plant Area |
n/a
|
Annual Production | 4,000,000
pieces
|
Production Hrs. Annual | 2,340
hrs
|
Location (State) | New Jersey |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $80,781 | 975,674 |
kWh
|
$0.083 |
Natural Gas | $9,473 | 1,432 |
MMBtu
|
$6.62 |
Fuel Oil #4 | $19,250 | 3,332 |
MMBtu
|
$5.78 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $21,623 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $3,654 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Natural Gas Savings | Fuel Oil #4 Savings | Paper Savings |
---|---|---|---|---|---|---|---|---|
01 | 2.2136: Install / repair insulation on steam lines | $1,782 | $3,857 | - | - |
$1,782
-
MMBtu
|
- | |
02 | 2.1233: Analyze flue gas for proper air/fuel ratio | $674 | $537 | - | - |
$674
-
MMBtu
|
- | |
03 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $6,478 | $2,138 |
$6,478
78,253
kWh
|
- | - | - | |
04 | 2.3191: Use demand controller or load shedder | $1,317 | $1,900 |
$1,317
40,445
kWh
|
- | - | - | |
05 | 2.1131: Repair faulty insulation in furnaces, boilers, etc | $158 | $260 | - | - |
$158
-
MMBtu
|
- | |
06 | 2.4312: Improve lubrication practices | $891 | $300 |
$891
10,844
kWh
|
- | - | - | |
07 | 2.1332: Convert combustion equipment to burn natural gas | $2,338 | $645 | - |
$(-142.0)
-
MMBtu
|
$2,480
-
MMBtu
|
- | |
08 | 3.6121: Burn waste paper for heat | $5,005 | $11,000 | - | - |
$6,249
-
MMBtu
|
$(-1,244.0)
-
MMBtu
|
|
09 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $467 | $150 |
$467
5,569
kWh
|
- | - | - | |
10 | 2.7441: Replace broken windows and/or window sash | $2,513 | $417 | - | - |
$2,513
-
MMBtu
|
- | |
TOTAL RECOMMENDED | $21,623 | $21,204 |
$9,153
135,111
kWh
|
$(-142.0)
-
MMBtu
|
$13,856
-
MMBtu
|
$(-1,244.0)
-
MMBtu
|
||
TOTAL IMPLEMENTED | $3,654 | $1,104 |
$467
5,569
kWh
|
- |
$3,187
-
MMBtu
|
- | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Natural Gas Savings | Fuel Oil #4 Savings | Paper Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs