Assessment Year | 2025 |
---|---|
Principal Product | Liquid painting, powder coating, silk screening |
NAICS | 325510: Paint and Coating Manufacturing |
SIC | 3479: Coating, Engraving, and Allied Services, Not Elsewhere Classified |
Sales Range | $5 M to 10M |
# of Employees | 35 |
Plant Area |
43,000
ft2
|
Annual Production | 1,000,000
units
|
Production Hrs. Annual | 2,080
hrs
|
Location (State) | California |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $110,854 | 413,809 |
kWh
|
$0.27 |
Electricity Demand | $49,225 | 2,303 |
kW-mo/yr
|
$21.37 |
Natural Gas | $147,448 | 7,371 |
MMBtu
|
$20.00 |
LPG | $1,236 | 43 |
MMBtu
|
$28.74 |
TOTAL YEARLY COSTS | $308,763 | |||
RECOMMENDED SAVINGS* | $137,778 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | - |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings |
---|---|---|---|---|---|---|---|
01 | 2.9114: Use solar heat to make electricty | $39,455 | $171,206 |
$37,421
139,629
kWh
|
$2,034
-
kW-mo/yr
|
- | |
02 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $14,291 | - |
$11,748
43,837
kWh
|
$2,543
-
kW-mo/yr
|
- | |
03 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $7,039 | $28,758 |
$4,881
18,211
kWh
|
$2,158
-
kW-mo/yr
|
- | |
04 | 2.7135: Install occupancy sensors | $5,502 | $3,262 |
$1,215
4,536
kWh
|
$4,287
-
kW-mo/yr
|
- | |
05 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $7,430 | $15,514 |
$5,154
19,239
kWh
|
$2,276
-
kW-mo/yr
|
- | |
06 | 2.7447: Install vinyl strip / high speed / air curtain doors | $48,587 | $3,938 |
$(-1,513.0)
(-5,646)
kWh
|
- |
$50,100
-
MMBtu
|
|
07 | 2.4231: Reduce the pressure of compressed air to the minimum required | $758 | - |
$630
2,351
kWh
|
$128
-
kW-mo/yr
|
- | |
08 | 2.4324: Replace hydraulic / pneumatic equipment with electric equipment | $1,332 | $4,500 |
$712
2,655
kWh
|
$620
-
kW-mo/yr
|
- | |
09 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $731 | $114 |
$517
1,929
kWh
|
$214
-
kW-mo/yr
|
- | |
10 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $12,653 | $10,067 |
$8,785
32,780
kWh
|
$3,868
-
kW-mo/yr
|
- | |
TOTAL RECOMMENDED | $137,778 | $237,359 |
$69,550
259,521
kWh
|
$18,128
-
kW-mo/yr
|
$50,100
-
MMBtu
|
||
TOTAL IMPLEMENTED | - | - | - | - | - | ||