Assessment Year | 2025 |
---|---|
Principal Product | Beer |
NAICS | 312120: Breweries |
SIC | 2082: Malt Beverages |
Sales Range | greater than $500 M |
# of Employees | 500 |
Plant Area |
958,320
ft2
|
Annual Production | 1,200,000
bbl
|
Production Hrs. Annual | 8,400
hrs
|
Location (State) | California |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | ||
---|---|---|---|---|---|
Electricity Usage | $769,436 | 3,682,044 |
kWh
|
$0.21 | |
Electricity Demand | $646,771 | 15,962 |
kW-mo/yr
|
$40.52 | |
Natural Gas | $1,529,072 | 166,221 |
MMBtu
|
$9.20 | |
Waste Disposal Costs | |||||
Water Usage | $104,921 | 108,368,789 |
Tgal
|
$0.001 | |
Water Disposal | $305,397 | 78,307,674 |
Tgal
|
$0.004 | |
TOTAL YEARLY COSTS | $3,355,597 | ||||
RECOMMENDED SAVINGS* | $362,533 |
See individual recommendations below
*Non-energy impacts included in savings.
|
|||
IMPLEMENTED SAVINGS* | - |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Water Usage Savings | Water Disposal Savings | Personnel Changes Savings |
---|---|---|---|---|---|---|---|---|---|---|
01 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $28,680 | - |
$29,880
142,968
kWh
|
- | - | - | - | $(-1,200.0) | |
02 | 2.6218: Turn off equipment when not in use | $3,867 | - |
$3,867
18,509
kWh
|
- | - | - | - | - | |
03 | 2.2135: Repair and eliminate steam leaks | $2,640 | - | - | - |
$3,740
-
MMBtu
|
- | - | $(-1,100.0) | |
04 | 2.6231: Utilize controls to operate equipment only when needed | $12,083 | $2,208 |
$12,083
57,813
kWh
|
- | - | - | - | - | |
05 | 2.6231: Utilize controls to operate equipment only when needed | $32,787 | $17,210 |
$25,689
122,923
kWh
|
$7,098
-
kW-mo/yr
|
- | - | - | - | |
06 | 2.2511: Insulate bare equipment | $3,235 | $4,152 |
$1,202
5,754
kWh
|
- |
$2,033
-
MMBtu
|
- | - | - | |
07 | 2.4239: Eliminate or reduce compressed air usage | $10,943 | $20,376 |
$10,943
52,361
kWh
|
- | - | - | - | - | |
08 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $32,940 | $114,566 |
$32,940
157,606
kWh
|
- | - | - | - | - | |
09 | 3.4151: Minimize water usage | $3,105 | $23,556 | - | - | - |
$619
-
Tgal
|
$2,486
-
Tgal
|
- | |
10 | 2.2622: Replace existing chiller with high efficiency model | $8,335 | $80,990 |
$8,335
39,885
kWh
|
- | - | - | - | - | |
11 | 2.9114: Use solar heat to make electricty | $223,918 | $872,791 |
$223,918
1,071,379
kWh
|
- | - | - | - | - | |
TOTAL RECOMMENDED | $362,533 | $1,135,849 |
$348,857
1,669,198
kWh
|
$7,098
-
kW-mo/yr
|
$5,773
-
MMBtu
|
$619
-
Tgal
|
$2,486
-
Tgal
|
$(-2,300.0) | ||
TOTAL IMPLEMENTED | - | - | - | - | - | - | - | - | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Water Usage Savings | Water Disposal Savings | Personnel Changes Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs