Assessment Year | 2022 |
---|---|
Principal Product | Peaches, Strawberries |
NAICS | 311411: Frozen Fruit, Juice, and Vegetable Manufacturing |
SIC | 2037: Frozen Fruits, Fruit Juices, and Vegetables |
Sales Range | $100 M to 500M |
# of Employees | 450 |
Plant Area |
850,000
ft2
|
Annual Production | 67,000,000
lb
|
Production Hrs. Annual | 8,760
hrs
|
Location (State) | California |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $2,155,539 | 29,682,000 |
kWh
|
$0.073 |
Electricity Demand | $615,372 | 60,966 |
kW-mo/yr
|
$10.09 |
Electricity Fees | $91,059 | - |
|
- |
Natural Gas | $264,706 | 32,519 |
MMBtu
|
$8.14 |
TOTAL YEARLY COSTS | $3,126,676 | |||
RECOMMENDED SAVINGS* | $153,220 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $65,945 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Personnel Changes Savings | One-time Revenue or Avoided Cost Savings |
---|---|---|---|---|---|---|---|---|---|
01 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $1,537 | - |
$2,617
35,033
kWh
|
- | - | $(-1,080.0) | - | |
02 | 2.7124: Make a practice of turning off lights when not needed | $9,922 | - |
$8,017
107,320
kWh
|
$1,905
-
kW-mo/yr
|
- | - | - | |
03 | 2.2162: Reduce excess steam bleeding | $9,616 | - | - | - |
$9,616
-
MMBtu
|
- | - | |
04 | 2.4235: Remove or close off unneeded compressed air lines | $6,698 | - |
$6,698
89,681
kWh
|
- | - | - | - | |
05 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $814 | $268 |
$684
9,158
kWh
|
$130
-
kW-mo/yr
|
- | - | - | |
06 | 2.6232: Install set-back timers | $22,648 | $6,467 |
$5,236
70,108
kWh
|
- |
$17,412
-
MMBtu
|
- | - | |
07 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $11,540 | $14,724 |
$8,954
119,878
kWh
|
$2,415
-
kW-mo/yr
|
- | $313 | $(-142.0) | |
08 | 2.2123: Insulate feedwater tank | $1,806 | $4,445 | - | - |
$1,806
-
MMBtu
|
- | - | |
09 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $5,521 | $18,051 |
$5,521
73,912
kWh
|
- | - | - | - | |
10 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $47,418 | $177,700 |
$47,418
634,886
kWh
|
- | - | - | - | |
11 | 3.6193: Install equipment (eg compactor) to reduce disposal costs | $35,700 | $132,000 | - | - | - | - | $35,700 | |
TOTAL RECOMMENDED | $153,220 | $353,655 |
$85,145
1,139,976
kWh
|
$4,450
-
kW-mo/yr
|
$28,834
-
MMBtu
|
$(-767.0) | $35,558 | ||
TOTAL IMPLEMENTED | $65,945 | $39,242 |
$34,426
460,899
kWh
|
$4,320
-
kW-mo/yr
|
$27,028
-
MMBtu
|
$313 | $(-142.0) | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Personnel Changes Savings | One-time Revenue or Avoided Cost Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs