Assessment Year | 2019 |
---|---|
Principal Product | Fabricated Metal Products |
NAICS | 332999: All Other Miscellaneous Fabricated Metal Product Manufacturing |
SIC | 3499: Fabricated Metal Products, Not Elsewhere Classified |
Sales Range | $10 M to 50M |
# of Employees | 70 |
Plant Area |
65,000
ft2
|
Annual Production | 25,000
units
|
Production Hrs. Annual | 4,394
hrs
|
Location (State) | California |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $132,823 | 639,172 |
kWh
|
$0.21 |
Electricity Demand | $26,504 | 1,478 |
kW-mo/yr
|
$17.93 |
TOTAL YEARLY COSTS | $159,327 | |||
RECOMMENDED SAVINGS* | $53,417 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $53,417 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Personnel Changes Savings |
---|---|---|---|---|---|---|---|
01 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $4,764 | - |
$5,364
25,815
kWh
|
- | $(-600.0) | |
02 | 2.4221: Install compressor air intakes in coolest locations | $193 | - |
$193
931
kWh
|
- | - | |
03 | 2.4231: Reduce the pressure of compressed air to the minimum required | $473 | $100 |
$473
2,277
kWh
|
- | - | |
04 | 2.4231: Reduce the pressure of compressed air to the minimum required | $2,363 | $300 |
$1,752
8,431
kWh
|
$611
-
kW-mo/yr
|
- | |
05 | 2.7224: Reduce space conditioning during non-working hours | $4,653 | $1,103 |
$4,653
22,391
kWh
|
- | - | |
06 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $1,047 | $2,930 |
$803
3,863
kWh
|
$243
-
kW-mo/yr
|
$1 | |
07 | 2.9114: Use solar heat to make electricty | $39,924 | $172,115 |
$39,924
192,125
kWh
|
- | - | |
TOTAL RECOMMENDED | $53,417 | $176,548 |
$53,162
255,833
kWh
|
$854
-
kW-mo/yr
|
$(-599.0) | ||
TOTAL IMPLEMENTED | $53,417 | $176,548 |
$53,162
255,833
kWh
|
$854
-
kW-mo/yr
|
$(-599.0) | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Personnel Changes Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs