Assessment Year | 2016 |
---|---|
Principal Product | Wine |
NAICS | 312130: Wineries |
SIC | 2084: Wines, Brandy, and Brandy Spirits |
Sales Range | $100 M to 500M |
# of Employees | 42 |
Plant Area |
370,260
ft2
|
Annual Production | 115,000
units
|
Production Hrs. Annual | 6,960
hrs
|
Location (State) | California |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $384,586 | 4,170,722 |
kWh
|
$0.092 |
Electricity Demand | $407,699 | 14,993 |
kW-mo/yr
|
$27.19 |
LPG | $68,043 | 4,606 |
MMBtu
|
$14.77 |
TOTAL YEARLY COSTS | $860,328 | |||
RECOMMENDED SAVINGS* | $62,883 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $45,027 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | LPG Savings |
---|---|---|---|---|---|---|---|
01 | 2.7224: Reduce space conditioning during non-working hours | $14,980 | - |
$14,980
162,455
kWh
|
- | - | |
02 | 2.4239: Eliminate or reduce compressed air usage | $5,509 | $840 |
$5,509
68,855
kWh
|
- | - | |
03 | 2.2511: Insulate bare equipment | $6,138 | $882 | - | - |
$6,138
-
MMBtu
|
|
04 | 2.4231: Reduce the pressure of compressed air to the minimum required | $464 | $70 |
$290
3,150
kWh
|
$174
-
kW-mo/yr
|
- | |
05 | 2.6231: Utilize controls to operate equipment only when needed | $1,183 | $1,469 |
$1,183
12,828
kWh
|
- | - | |
06 | 2.6231: Utilize controls to operate equipment only when needed | $582 | $1,469 |
$582
6,314
kWh
|
- | - | |
07 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $17,217 | $44,943 |
$16,332
177,118
kWh
|
$885
-
kW-mo/yr
|
- | |
08 | 2.2621: Modify refrigeration system to operate at a lower pressure | $16,810 | $61,903 |
$16,810
182,694
kWh
|
- | - | |
TOTAL RECOMMENDED | $62,883 | $111,576 |
$55,686
613,414
kWh
|
$1,059
-
kW-mo/yr
|
$6,138
-
MMBtu
|
||
TOTAL IMPLEMENTED | $45,027 | $48,134 |
$38,004
421,256
kWh
|
$885
-
kW-mo/yr
|
$6,138
-
MMBtu
|
||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | LPG Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs