Assessment Year | 2014 |
---|---|
Principal Product | Wine |
NAICS | 312130: Wineries |
SIC | 2084: Wines, Brandy, and Brandy Spirits |
Sales Range | $10 M to 50M |
# of Employees | 35 |
Plant Area |
305,000
ft2
|
Annual Production | 4,800,000
pieces
|
Production Hrs. Annual | 3,783
hrs
|
Location (State) | California |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $139,376 | 1,514,918 |
kWh
|
$0.092 |
Electricity Demand | $110,453 | 4,947 |
kW-mo/yr
|
$22.33 |
Electricity Fees | $7,960 | - |
|
- |
Natural Gas | $31,803 | 3,947 |
MMBtu
|
$8.06 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $77,624 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $12,013 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Administrative Changes Savings |
---|---|---|---|---|---|---|---|---|
01 | 2.7224: Reduce space conditioning during non-working hours | $6,757 | - |
$735
7,241
kWh
|
- |
$6,022
-
MMBtu
|
- | |
02 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $2,693 | $650 |
$2,693
26,517
kWh
|
- | - | - | |
03 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $29,874 | $19,111 |
$29,874
294,176
kWh
|
- | - | - | |
04 | 2.4226: Use / purchase optimum sized compressor | $30,675 | $77,383 |
$8,885
87,493
kWh
|
$7,340
-
kW-mo/yr
|
- | $14,450 | |
05 | 2.6212: Turn off equipment during breaks, reduce operating time | $5,062 | $12,000 |
$4,085
40,224
kWh
|
$977
-
kW-mo/yr
|
- | - | |
06 | 2.7135: Install occupancy sensors | $2,563 | $11,811 |
$1,516
14,929
kWh
|
$1,047
-
kW-mo/yr
|
- | - | |
TOTAL RECOMMENDED | $77,624 | $120,955 |
$47,788
470,580
kWh
|
$9,364
-
kW-mo/yr
|
$6,022
-
MMBtu
|
$14,450 | ||
TOTAL IMPLEMENTED | $12,013 | $12,461 |
$4,944
48,687
kWh
|
$1,047
-
kW-mo/yr
|
$6,022
-
MMBtu
|
- | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Administrative Changes Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs