Assessment Year | 2013 |
---|---|
Principal Product | fast food serving containers |
NAICS | 322212: Folding Paperboard Box Manufacturing |
SIC | 2657: Folding Paperboard Boxes, Including Sanitary |
Sales Range | $10 M to 50M |
# of Employees | 150 |
Plant Area |
172,000
ft2
|
Annual Production | 1
units
|
Production Hrs. Annual | 6,624
hrs
|
Location (State) | California |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $383,340 | 5,514,005 |
kWh
|
$0.070 |
Electricity Demand | $147,151 | 11,884 |
kW-mo/yr
|
$12.38 |
Electricity Fees | $8,966 | - |
|
- |
Natural Gas | $138,334 | 21,382 |
MMBtu
|
$6.47 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $44,043 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $28,084 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings |
---|---|---|---|---|---|---|---|
01 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $9,414 | $840 |
$9,414
135,448
kWh
|
- | - | |
02 | 2.7264: Interlock heating and air conditioning systems to prevent simultaneous operation | $4,345 | $2,494 |
$3,493
50,252
kWh
|
$852
-
kW-mo/yr
|
- | |
03 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $6,090 | $4,441 |
$5,582
80,314
kWh
|
$508
-
kW-mo/yr
|
- | |
04 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $176 | $105 |
$133
1,916
kWh
|
$43
-
kW-mo/yr
|
- | |
05 | 2.7264: Interlock heating and air conditioning systems to prevent simultaneous operation | $3,906 | $4,995 |
$2,953
42,491
kWh
|
$953
-
kW-mo/yr
|
- | |
06 | 2.7264: Interlock heating and air conditioning systems to prevent simultaneous operation | $4,153 | $5,267 |
$4,153
59,760
kWh
|
- | - | |
07 | 2.1311: Replace electrically-operated equipment with fossil fuel equipment | $6,126 | $11,332 |
$7,233
104,069
kWh
|
$1,765
-
kW-mo/yr
|
$(-2,872.0)
-
MMBtu
|
|
08 | 2.1311: Replace electrically-operated equipment with fossil fuel equipment | $4,281 | $7,509 |
$4,143
59,616
kWh
|
$1,783
-
kW-mo/yr
|
$(-1,645.0)
-
MMBtu
|
|
09 | 2.6218: Turn off equipment when not in use | $799 | $2,008 |
$799
11,501
kWh
|
- | - | |
10 | 2.7135: Install occupancy sensors | $2,748 | $8,715 |
$1,994
28,698
kWh
|
$754
-
kW-mo/yr
|
- | |
11 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $2,005 | $10,308 |
$1,515
21,795
kWh
|
$490
-
kW-mo/yr
|
- | |
TOTAL RECOMMENDED | $44,043 | $58,014 |
$41,412
595,860
kWh
|
$7,148
-
kW-mo/yr
|
$(-4,517.0)
-
MMBtu
|
||
TOTAL IMPLEMENTED | $28,084 | $18,142 |
$25,728
370,181
kWh
|
$2,356
-
kW-mo/yr
|
- | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs