Assessment Year | 2013 |
---|---|
Principal Product | Screen and Digital Printing |
NAICS | 323113: Commercial Screen Printing |
SIC | 2759: Commercial Printing, Not Elsewhere Classified |
Sales Range | $10 M to 50M |
# of Employees | 60 |
Plant Area |
65,000
ft2
|
Annual Production | 100
units
|
Production Hrs. Annual | 4,160
hrs
|
Location (State) | California |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $188,268 | 995,642 |
kWh
|
$0.19 |
Natural Gas | $2,789 | 229 |
MMBtu
|
$12.18 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $58,995 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $29,910 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Fees Savings | Natural Gas Savings |
---|---|---|---|---|---|---|---|
01 | 2.7221: Lower temperature during the winter season and vice-versa | $911 | - |
$694
3,671
kWh
|
- |
$217
-
MMBtu
|
|
02 | 2.4231: Reduce the pressure of compressed air to the minimum required | $620 | - |
$620
3,279
kWh
|
- | - | |
03 | 2.7135: Install occupancy sensors | $3,792 | $6,796 |
$3,792
20,050
kWh
|
- | - | |
04 | 2.4221: Install compressor air intakes in coolest locations | $425 | $729 |
$425
2,245
kWh
|
- | - | |
05 | 2.1311: Replace electrically-operated equipment with fossil fuel equipment | $354 | $1,395 |
$488
2,582
kWh
|
- |
$(-134.0)
-
MMBtu
|
|
06 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $6,497 | $14,135 |
$6,766
37,202
kWh
|
$(-269.0) | - | |
07 | 2.8114: Change rate schedules or other changes in utility service | $28,111 | $46,338 | - | $28,111 | - | |
08 | 3.6193: Install equipment (eg compactor) to reduce disposal costs | $15,796 | $43,156 | - | $15,796 | - | |
09 | 3.5315: Lease / purchase baler; sell cardboard to recycler | $2,489 | $13,500 | - | $2,489 | - | |
TOTAL RECOMMENDED | $58,995 | $126,049 |
$12,785
69,029
kWh
|
$46,127 |
$83
-
MMBtu
|
||
TOTAL IMPLEMENTED | $29,910 | $78,316 |
$11,677
63,168
kWh
|
$18,016 |
$217
-
MMBtu
|
||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Fees Savings | Natural Gas Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs