| Assessment Year | 2013 |
|---|---|
| Principal Product | electroplating |
| NAICS | 332813: Electroplating, Plating, Polishing, Anodizing, and Coloring |
| SIC | 3471: Electroplating, Plating, Polishing, Anodizing, and Coloring |
| Sales Range | $1 M to 5M |
| # of Employees | 11 |
| Plant Area |
17,600
ft2
|
| Annual Production | 3,500
pieces
|
| Production Hrs. Annual | 3,504
hrs
|
| Location (State) | California |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $33,457 | 268,207 |
kWh
|
$0.12 |
| Electricity Demand | $9,339 | 1,027 |
kW-mo/yr
|
$9.09 |
| Natural Gas | $2,504 | 246 |
MMBtu
|
$10.16 |
| TOTAL YEARLY COSTS | - | |||
| RECOMMENDED SAVINGS* | $13,987 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | $438 | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Natural Gas Savings |
|---|---|---|---|---|---|---|---|---|
| 01 | 2.2514: Cover open tanks | $6,314 | $150 |
$6,058
48,583
kWh
|
$256
-
kW-mo/yr
|
- | - | |
| 02 | 2.7224: Reduce space conditioning during non-working hours | $438 | - |
$315
2,525
kWh
|
- | - |
$123
-
MMBtu
|
|
| 03 | 2.4224: Upgrade controls on compressors | $2,488 | $3,272 |
$2,488
19,953
kWh
|
- | - | - | |
| 04 | 2.7135: Install occupancy sensors | $864 | $2,751 |
$657
5,266
kWh
|
$207
-
kW-mo/yr
|
- | - | |
| 05 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $3,275 | $12,405 |
$2,271
18,212
kWh
|
$389
-
kW-mo/yr
|
$615 | - | |
| 06 | 2.1311: Replace electrically-operated equipment with fossil fuel equipment | $608 | $2,400 |
$744
5,967
kWh
|
$123
-
kW-mo/yr
|
- |
$(-259.0)
-
MMBtu
|
|
| TOTAL RECOMMENDED | $13,987 | $20,978 |
$12,533
100,506
kWh
|
$975
-
kW-mo/yr
|
$615 |
$(-136.0)
-
MMBtu
|
||
| TOTAL IMPLEMENTED | $438 | - |
$315
2,525
kWh
|
- | - |
$123
-
MMBtu
|
||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Natural Gas Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs