Assessment Year | 2013 |
---|---|
Principal Product | Energy Recovery Devices for Water Desalination |
NAICS | 333911: Pump and Pumping Equipment Manufacturing |
SIC | 3559: Special Industry Machinery, Not Elsewhere Classified |
Sales Range | $10 M to 50M |
# of Employees | 90 |
Plant Area |
177,000
ft2
|
Annual Production | 1,700
pieces
|
Production Hrs. Annual | 4,845
hrs
|
Location (State) | California |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $229,451 | 2,425,794 |
kWh
|
$0.095 |
Electricity Demand | $123,996 | 7,937 |
kW-mo/yr
|
$15.62 |
Natural Gas | $98,458 | 13,448 |
MMBtu
|
$7.32 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $49,334 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $38,405 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings |
---|---|---|---|---|---|---|---|
01 | 2.7224: Reduce space conditioning during non-working hours | $4,421 | - |
$530
5,927
kWh
|
- |
$3,891
-
MMBtu
|
|
02 | 3.7312: Implement a regular maintenance program to reduce emissions from leaky valves and pipe fittings | $1,697 | $768 |
$1,697
18,987
kWh
|
- | - | |
03 | 2.7111: Reduce illumination to minimum necessary levels | $6,822 | $885 |
$4,313
48,242
kWh
|
$2,509
-
kW-mo/yr
|
- | |
04 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $25,465 | $16,491 |
$18,100
202,456
kWh
|
$7,365
-
kW-mo/yr
|
- | |
05 | 2.7135: Install occupancy sensors | $6,727 | $9,958 |
$4,405
49,278
kWh
|
$2,322
-
kW-mo/yr
|
- | |
06 | 2.6231: Utilize controls to operate equipment only when needed | $841 | $2,072 |
$841
9,403
kWh
|
- | - | |
07 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $1,332 | $4,481 |
$1,332
16,302
kWh
|
- | - | |
08 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $2,029 | $5,603 |
$917
10,261
kWh
|
$1,112
-
kW-mo/yr
|
- | |
TOTAL RECOMMENDED | $49,334 | $40,258 |
$32,135
360,856
kWh
|
$13,308
-
kW-mo/yr
|
$3,891
-
MMBtu
|
||
TOTAL IMPLEMENTED | $38,405 | $18,144 |
$24,640
275,612
kWh
|
$9,874
-
kW-mo/yr
|
$3,891
-
MMBtu
|
||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs