| Assessment Year | 2013 |
|---|---|
| Principal Product | Polyethylene Foam |
| NAICS | 326150: Urethane and Other Foam Product (except Polystyrene) Manufacturing |
| SIC | 3086: Plastics Foam Products |
| Sales Range | $10 M to 50M |
| # of Employees | 59 |
| Plant Area |
277,000
ft2
|
| Annual Production | 50,000,000
lb
|
| Production Hrs. Annual | 6,048
hrs
|
| Location (State) | California |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $561,783 | 6,455,930 |
kWh
|
$0.087 |
| Electricity Demand | $289,147 | 17,316 |
kW-mo/yr
|
$16.70 |
| Electricity Fees | $16,667 | - |
|
- |
| Natural Gas | $79,529 | 10,064 |
MMBtu
|
$7.90 |
| TOTAL YEARLY COSTS | - | |||
| RECOMMENDED SAVINGS* | $65,183 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | $28,050 | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Natural Gas Savings |
|---|---|---|---|---|---|---|---|---|
| 01 | 2.6222: Use drying oven (batch type) on alternate days or other optimum schedule to run equipment with full loads | $6,713 | - |
$6,713
77,351
kWh
|
- | - | - | |
| 02 | 2.4226: Use / purchase optimum sized compressor | $15,421 | $7,471 |
$15,421
175,187
kWh
|
- | - | - | |
| 03 | 2.7224: Reduce space conditioning during non-working hours | $4,974 | $5,906 |
$2,648
30,432
kWh
|
- | - |
$2,326
-
MMBtu
|
|
| 04 | 2.4131: Size electric motors for peak operating efficiency | $1,255 | $2,240 |
$1,255
14,425
kWh
|
- | - | - | |
| 05 | 2.4131: Size electric motors for peak operating efficiency | $30,904 | $9,885 |
$30,904
44,862
kWh
|
- | - | - | |
| 06 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $1,808 | $7,235 |
$1,808
16,860
kWh
|
- | - | - | |
| 07 | 2.7135: Install occupancy sensors | $3,416 | $13,849 |
$2,344
26,931
kWh
|
$1,072
-
kW-mo/yr
|
- | - | |
| 08 | 2.3111: Heat water during off-peak periods and store for later use | $692 | $2,830 | - | - | $692 | - | |
| TOTAL RECOMMENDED | $65,183 | $49,416 |
$61,093
386,048
kWh
|
$1,072
-
kW-mo/yr
|
$692 |
$2,326
-
MMBtu
|
||
| TOTAL IMPLEMENTED | $28,050 | $31,385 |
$26,286
296,329
kWh
|
$1,072
-
kW-mo/yr
|
$692 | - | ||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Natural Gas Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs