Assessment Year 2009
Principal Product Cardboard Boxes
NAICS 322212: Folding Paperboard Box Manufacturing
SIC 2657: Folding Paperboard Boxes, Including Sanitary
Sales Range $100
M
to 500
M
# of Employees 345
Plant Area 520,000
ft2
Annual Production 1
units
Production Hrs. Annual 8,736
hrs
Location (State) California

Facility Energy Cost and Usage

Source Yearly Cost Usage
Electricity Usage $1,159,474 11,479,838
kWh
Electricity Demand $435,656 2,600
kW-mo/yr
Electricity Fees $15,085 -
Natural Gas $99,033 8,254
MMBtu
TOTAL YEARLY COSTS -
RECOMMENDED SAVINGS* $167,451 *Non-energy impacts included in savings.
IMPLEMENTED SAVINGS* $105,019

Recommendations

# Description Yearly Savings* Imp'd Cost* Status Electricity Usage Savings Electricity Demand Savings Natural Gas Savings
01 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves $3,246 - $3,246
58,184
kWh
- -
02 2.2511: Insulate bare equipment $2,383 $460 - - $2,383
-
MMBtu
03 2.6231: Utilize controls to operate equipment only when needed $34,176 $37,453 $34,176
501,330
kWh
- -
04 2.1311: Replace electrically-operated equipment with fossil fuel equipment $26,893 $32,381 $19,298
283,080
kWh
$7,595
-
kW-mo/yr
-
05 2.6231: Utilize controls to operate equipment only when needed $1,172 $3,307 $1,172
17,188
kWh
- -
06 2.7142: Utilize higher efficiency lamps and/or ballasts $75,147 $244,092 $53,813
789,387
kWh
$21,334
-
kW-mo/yr
-
07 2.7135: Install occupancy sensors $10,418 $41,832 $10,418
109,663
kWh
- -
08 2.6231: Utilize controls to operate equipment only when needed $191 $945 $191
2,797
kWh
- -
09 2.1311: Replace electrically-operated equipment with fossil fuel equipment $3,842 $12,018 $2,757
40,440
kWh
$1,085
-
kW-mo/yr
-
10 2.2122: Install / repair insulation on condensate lines $9,983 $67,481 $1,212
17,795
kWh
$648
-
kW-mo/yr
$8,123
-
MMBtu
TOTAL RECOMMENDED $167,451 $439,969 $126,283
1,819,864
kWh
$30,662
-
kW-mo/yr
$10,506
-
MMBtu
TOTAL IMPLEMENTED $105,019 $365,883 $71,446
1,015,469
kWh
$23,067
-
kW-mo/yr
$10,506
-
MMBtu
Yearly Savings* Imp'd Cost* Electricity Usage Savings Electricity Demand Savings Natural Gas Savings
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs