Assessment Year | 2009 |
---|---|
Principal Product | Citrus Juice and Oil |
NAICS | 311411: Frozen Fruit, Juice, and Vegetable Manufacturing |
SIC | 2037: Frozen Fruits, Fruit Juices, and Vegetables |
Sales Range | less than $500 k |
# of Employees | 130 |
Plant Area |
80,000
ft2
|
Annual Production | 500,000
ton
|
Production Hrs. Annual | 7,488
hrs
|
Location (State) | California |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $944,457 | 8,597,325 |
kWh
|
$0.11 |
Electricity Demand | $417,327 | 76,974 |
kW-mo/yr
|
$5.42 |
Natural Gas | $1,432,584 | 140,957 |
MMBtu
|
$10.16 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $398,349 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $361,016 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Water Disposal Savings |
---|---|---|---|---|---|---|---|---|
01 | 2.2135: Repair and eliminate steam leaks | $45,410 | - | - | - |
$45,410
-
MMBtu
|
- | |
02 | 2.1233: Analyze flue gas for proper air/fuel ratio | $13,699 | - | - | - |
$13,699
-
MMBtu
|
- | |
03 | 2.1241: Reduce excessive boiler blowdown | $10,627 | $2,372 | - | - |
$10,627
-
MMBtu
|
- | |
04 | 2.6231: Utilize controls to operate equipment only when needed | $9,963 | $2,837 |
$9,963
90,698
kWh
|
- | - | - | |
05 | 2.7132: Install timers on light switches in little used areas | $5,402 | $3,037 |
$5,061
46,071
kWh
|
$341
-
kW-mo/yr
|
- | - | |
06 | 2.4222: Install adequate dryers on air lines to eliminate blowdown | $15,888 | $9,574 |
$15,888
144,634
kWh
|
- | - | - | |
07 | 2.2621: Modify refrigeration system to operate at a lower pressure | $17,939 | $12,500 |
$17,939
163,305
kWh
|
- | - | - | |
08 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $48,237 | $33,968 |
$48,237
439,113
kWh
|
- | - | - | |
09 | 2.6231: Utilize controls to operate equipment only when needed | $51,835 | $40,007 |
$51,835
471,870
kWh
|
- | - | - | |
10 | 2.7134: Use photocell controls | $18,403 | $18,196 |
$18,403
167,525
kWh
|
- | - | - | |
11 | 2.4133: Use most efficient type of electric motors | $3,553 | $5,659 |
$3,553
32,344
kWh
|
- | - | - | |
12 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $2,489 | $4,385 |
$2,245
20,433
kWh
|
$244
-
kW-mo/yr
|
- | - | |
13 | 2.4323: Use optimum size and capacity equipment | $2,217 | $4,719 |
$2,217
20,181
kWh
|
- | - | - | |
14 | 2.7135: Install occupancy sensors | $701 | $1,567 |
$701
6,378
kWh
|
- | - | - | |
15 | 2.1233: Analyze flue gas for proper air/fuel ratio | $13,809 | $31,988 |
$13,809
47,758
kWh
|
- | - | - | |
16 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $9,002 | $318 |
$8,279
75,634
kWh
|
$723
-
kW-mo/yr
|
- | - | |
17 | 2.4324: Replace hydraulic / pneumatic equipment with electric equipment | $89,029 | $326,072 |
$66,495
605,328
kWh
|
$22,534
-
kW-mo/yr
|
- | - | |
18 | 2.1243: Use heat from boiler blowdown to preheat boiler feed water | $16,622 | $86,476 | - | - |
$16,622
-
MMBtu
|
- | |
19 | 3.4115: Recover and reuse cooling water | $23,524 | $15,018 | - | - | - |
$23,524
-
Tgal
|
|
TOTAL RECOMMENDED | $398,349 | $598,693 |
$264,625
2,331,272
kWh
|
$23,842
-
kW-mo/yr
|
$86,358
-
MMBtu
|
$23,524
-
Tgal
|
||
TOTAL IMPLEMENTED | $361,016 | $551,687 |
$250,816
2,283,514
kWh
|
$23,842
-
kW-mo/yr
|
$86,358
-
MMBtu
|
- | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Water Disposal Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs