Assessment Year | 2009 |
---|---|
Principal Product | Beverage closures and decorative capsules |
NAICS | 332119: Metal Crown, Closure, and Other Metal Stamping (except Automotive) |
SIC | 3466: Crowns and Closures |
Sales Range | $10 M to 50M |
# of Employees | 94 |
Plant Area |
60,000
ft2
|
Annual Production | 1
units
|
Production Hrs. Annual | 6,240
hrs
|
Location (State) | California |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $218,054 | 3,161,961 |
kWh
|
$0.069 |
Natural Gas | $59,921 | 4,662 |
MMBtu
|
$12.85 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $37,196 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $28,857 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Natural Gas Savings |
---|---|---|---|---|---|---|
01 | 2.7221: Lower temperature during the winter season and vice-versa | $6,854 | - |
$1,508
21,695
kWh
|
$5,346
-
MMBtu
|
|
02 | 2.2135: Repair and eliminate steam leaks | $850 | $360 |
$850
12,174
kWh
|
- | |
03 | 2.6218: Turn off equipment when not in use | $331 | - |
$35
505
kWh
|
$296
-
MMBtu
|
|
04 | 2.6231: Utilize controls to operate equipment only when needed | $265 | - |
$265
3,798
kWh
|
- | |
05 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $366 | $417 |
$366
5,237
kWh
|
- | |
06 | 2.7133: Use separate switches on perimeter lighting which may be turned off when natural light is available | $730 | $1,240 |
$730
10,451
kWh
|
- | |
07 | 2.7135: Install occupancy sensors | $1,052 | $2,064 |
$1,052
15,055
kWh
|
- | |
08 | 2.2511: Insulate bare equipment | $598 | $1,218 |
$598
8,573
kWh
|
- | |
09 | 2.4133: Use most efficient type of electric motors | $3,056 | $15,973 |
$3,056
43,747
kWh
|
- | |
10 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $7,741 | $38,621 |
$7,741
110,834
kWh
|
- | |
11 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $15,353 | $133,125 |
$15,353
219,800
kWh
|
- | |
TOTAL RECOMMENDED | $37,196 | $193,018 |
$31,554
451,869
kWh
|
$5,642
-
MMBtu
|
||
TOTAL IMPLEMENTED | $28,857 | $153,179 |
$23,215
332,462
kWh
|
$5,642
-
MMBtu
|
||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Natural Gas Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs