| Assessment Year | 2008 |
|---|---|
| Principal Product | Building Supply |
| NAICS | 321918: Other Millwork (including Flooring) |
| SIC | 2431: Millwork |
| Sales Range | $10 M to 50M |
| # of Employees | 72 |
| Plant Area |
54,000
ft2
|
| Annual Production | 1
pieces
|
| Production Hrs. Annual | 2,860
hrs
|
| Location (State) | Hawaii |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $197,789 | 544,920 |
kWh
|
$0.36 |
| Electricity Demand | $21,477 | 3,068 |
kW-mo/yr
|
$7.00 |
| Electricity Fees | $86,177 | - |
|
- |
| Other Gas | $19,513 | 944 |
MMBtu
|
$20.67 |
| TOTAL YEARLY COSTS | - | |||
| RECOMMENDED SAVINGS* | $28,186 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | $16,905 | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings |
|---|---|---|---|---|---|---|
| 01 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $10,775 | - |
$10,775
37,928
kWh
|
- | |
| 02 | 2.6231: Utilize controls to operate equipment only when needed | $4,455 | $452 |
$4,455
14,303
kWh
|
- | |
| 03 | 2.4133: Use most efficient type of electric motors | $3,202 | $1,339 |
$2,867
9,946
kWh
|
$335
-
kW-mo/yr
|
|
| 04 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $176 | $93 |
$151
503
kWh
|
$25
-
kW-mo/yr
|
|
| 05 | 2.6231: Utilize controls to operate equipment only when needed | $2,839 | $2,119 |
$2,839
9,847
kWh
|
- | |
| 06 | 2.6231: Utilize controls to operate equipment only when needed | $2,476 | $2,404 |
$2,476
8,587
kWh
|
- | |
| 07 | 2.4231: Reduce the pressure of compressed air to the minimum required | $3,134 | $4,709 |
$3,036
9,843
kWh
|
$98
-
kW-mo/yr
|
|
| 08 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $853 | $2,892 |
$853
2,958
kWh
|
- | |
| 09 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $276 | $953 |
$251
220
kWh
|
$25
-
kW-mo/yr
|
|
| TOTAL RECOMMENDED | $28,186 | $14,961 |
$27,703
94,135
kWh
|
$483
-
kW-mo/yr
|
||
| TOTAL IMPLEMENTED | $16,905 | $4,789 |
$16,520
57,184
kWh
|
$385
-
kW-mo/yr
|
||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs