Assessment Year | 2006 |
---|---|
Principal Product | Drugs of Abuse Test Kits |
NAICS | 325412: Pharmaceutical Preparation Manufacturing |
SIC | 2835: In Vitro and In Vivo Diagnostic Substances |
Sales Range | $50 M to 100M |
# of Employees | 270 |
Plant Area |
110,000
ft2
|
Annual Production | 45,000,000
pieces
|
Production Hrs. Annual | 2,340
hrs
|
Location (State) | California |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $419,309 | 4,532,100 |
kWh
|
$0.093 |
Electricity Demand | $128,641 | 9,396 |
kW-mo/yr
|
$13.69 |
Natural Gas | $83,604 | 7,044 |
MMBtu
|
$11.87 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $31,471 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $3,812 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings |
---|---|---|---|---|---|---|
01 | 2.7224: Reduce space conditioning during non-working hours | $16 | - |
$16
180
kWh
|
- | |
02 | 2.7314: Reduce ventilation air | $202 | - |
$202
2
kWh
|
- | |
03 | 2.7241: Install outside air damper / economizer on hvac unit | $882 | $24,000 |
$882
882
kWh
|
- | |
04 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $2,827 | $5,934 |
$8
94
kWh
|
$2,819
-
kW-mo/yr
|
|
05 | 2.1311: Replace electrically-operated equipment with fossil fuel equipment | $22,164 | $15,000 |
$10
109
kWh
|
$22,154
-
kW-mo/yr
|
|
06 | 2.8114: Change rate schedules or other changes in utility service | $31 | $29,700 |
$31
-
kWh
|
- | |
07 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $883 | $4,374 |
$3
38
kWh
|
$880
-
kW-mo/yr
|
|
08 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $872 | $2,849 |
$2
30
kWh
|
$870
-
kW-mo/yr
|
|
09 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $2 | $7,040 |
$1
15,233
kWh
|
$1
-
kW-mo/yr
|
|
10 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $234 | $557 |
$142
1
kWh
|
$92
-
kW-mo/yr
|
|
11 | 2.7111: Reduce illumination to minimum necessary levels | $955 | $2,480 |
$499
5
kWh
|
$456
-
kW-mo/yr
|
|
12 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $2,076 | $16,625 |
$2
24
kWh
|
$2,074
-
kW-mo/yr
|
|
13 | 2.4222: Install adequate dryers on air lines to eliminate blowdown | $327 | $6,381 |
$95
10
kWh
|
$232
-
kW-mo/yr
|
|
TOTAL RECOMMENDED | $31,471 | $114,940 |
$1,893
16,608
kWh
|
$29,578
-
kW-mo/yr
|
||
TOTAL IMPLEMENTED | $3,812 | $33,083 |
$957
15,455
kWh
|
$2,855
-
kW-mo/yr
|
||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs