Assessment Year | 2005 |
---|---|
Principal Product | Diced Tomatoes and Tomato Paste |
NAICS | 311421: Fruit and Vegetable Canning |
SIC | 2033: Canned Fruits, Vegetables, Preserves, Jams, and Jellies |
Sales Range | $100 M to 500M |
# of Employees | 297 |
Plant Area |
1,000,000
ft2
|
Annual Production | 143,000,000
lb
|
Production Hrs. Annual | 3,608
hrs
|
Location (State) | California |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $81,719 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $56,496 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings |
---|---|---|---|---|---|---|---|
01 | 2.6231: Utilize controls to operate equipment only when needed | $8,282 | $2,199 |
$8,282
53,890
kWh
|
- | - | |
02 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $4,696 | $1,952 |
$3,723
46,545
kWh
|
$973
-
kW-mo/yr
|
- | |
03 | 2.7135: Install occupancy sensors | $2,201 | - |
$1,202
15,027
kWh
|
$999
-
kW-mo/yr
|
- | |
04 | 2.1113: Reduce combustion air flow to optimum | $28,197 | $19,158 |
$4,930
61,639
kWh
|
$2,396
-
kW-mo/yr
|
$20,871
-
MMBtu
|
|
05 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $232 | $472 |
$183
2,284
kWh
|
$49
-
kW-mo/yr
|
- | |
06 | 2.4133: Use most efficient type of electric motors | $8,229 | $8,237 |
$4,359
54,497
kWh
|
$3,870
-
kW-mo/yr
|
- | |
07 | 2.7134: Use photocell controls | $3,343 | $11,115 |
$2,691
33,645
kWh
|
$652
-
kW-mo/yr
|
- | |
08 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $19,447 | $79,682 |
$17,111
149,760
kWh
|
$2,336
-
kW-mo/yr
|
- | |
09 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $7,092 | $39,414 |
$5,710
71,388
kWh
|
$1,382
-
kW-mo/yr
|
- | |
10 | 3.1222: Reduce water use with counter current rinsing | - | $95 | - | - | - | |
11 | 3.5315: Lease / purchase baler; sell cardboard to recycler | - | $10,000 | - | - | - | |
12 | 3.6193: Install equipment (eg compactor) to reduce disposal costs | - | $16,945 | - | - | - | |
TOTAL RECOMMENDED | $81,719 | $189,269 |
$48,191
488,675
kWh
|
$12,657
-
kW-mo/yr
|
$20,871
-
MMBtu
|
||
TOTAL IMPLEMENTED | $56,496 | $81,055 |
$27,004
287,959
kWh
|
$8,621
-
kW-mo/yr
|
$20,871
-
MMBtu
|
||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs