Assessment Year | 2004 |
---|---|
Principal Product | Herbs and Tea |
NAICS | 311942: Spice and Extract Manufacturing |
SIC | 2099: Food Preparations, Not Elsewhere Classified |
Sales Range | $5 M to 10M |
# of Employees | 55 |
Plant Area |
141,067
ft2
|
Annual Production | 2,000,000
lb
|
Production Hrs. Annual | 2,385
hrs
|
Location (State) | California |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $73,458 | 627,429 |
kWh
|
$0.12 |
Electricity Demand | $17,846 | 4,392 |
kW-mo/yr
|
$4.06 |
Natural Gas | $2,802 | 305 |
MMBtu
|
$9.19 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $13,937 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $4,007 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings |
---|---|---|---|---|---|---|
01 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $2,525 | - |
$2,525
25,996
kWh
|
- | |
02 | 2.4231: Reduce the pressure of compressed air to the minimum required | $1,594 | - |
$1,107
9,456
kWh
|
$487
-
kW-mo/yr
|
|
03 | 2.7111: Reduce illumination to minimum necessary levels | $808 | - |
$688
5,876
kWh
|
$120
-
kW-mo/yr
|
|
04 | 2.4226: Use / purchase optimum sized compressor | $674 | - |
$556
4,744
kWh
|
$118
-
kW-mo/yr
|
|
05 | 2.7135: Install occupancy sensors | $858 | $2,022 |
$584
4,983
kWh
|
$274
-
kW-mo/yr
|
|
06 | 2.4324: Replace hydraulic / pneumatic equipment with electric equipment | $218 | $586 |
$185
1,580
kWh
|
$33
-
kW-mo/yr
|
|
07 | 2.4133: Use most efficient type of electric motors | $579 | $2,142 |
$493
4,214
kWh
|
$86
-
kW-mo/yr
|
|
08 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $568 | $866 |
$484
4,132
kWh
|
$84
-
kW-mo/yr
|
|
09 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $6,113 | $52,546 |
$5,200
44,406
kWh
|
$913
-
kW-mo/yr
|
|
TOTAL RECOMMENDED | $13,937 | $58,162 |
$11,822
105,387
kWh
|
$2,115
-
kW-mo/yr
|
||
TOTAL IMPLEMENTED | $4,007 | - |
$3,769
36,616
kWh
|
$238
-
kW-mo/yr
|
||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs