Assessment Year | 1999 |
---|---|
Principal Product | Cans |
NAICS |
n/a
|
SIC | 3829: Measuring and Controlling Devices, Not Elsewhere Classified |
Sales Range | $50 M to 100M |
# of Employees | 110 |
Plant Area |
62,000
ft2
|
Annual Production | 400,000,000
pieces
|
Production Hrs. Annual | 7,488
hrs
|
Location (State) | California |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $165,091 | 4,311,254 |
kWh
|
$0.038 |
Electricity Demand | $74,653 | 10,665 |
kW-mo/yr
|
$7.00 |
Natural Gas | $30,614 | 6,115 |
MMBtu
|
$5.01 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $34,278 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $26,417 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Solid Waste (non-haz) Savings |
---|---|---|---|---|---|---|---|---|
01 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $6,720 | - |
$5,174
135,111
kWh
|
$1,546
-
kW-mo/yr
|
- | - | |
02 | 2.4239: Eliminate or reduce compressed air usage | $4,207 | $1,400 |
$3,241
84,701
kWh
|
$966
-
kW-mo/yr
|
- | - | |
03 | 2.6231: Utilize controls to operate equipment only when needed | $2,405 | $1,100 |
$1,778
46,600
kWh
|
$627
-
kW-mo/yr
|
- | - | |
04 | 2.4239: Eliminate or reduce compressed air usage | $1,977 | - |
$1,522
39,859
kWh
|
$455
-
kW-mo/yr
|
- | - | |
05 | 2.4133: Use most efficient type of electric motors | $977 | $1,439 |
$723
18,757
kWh
|
$254
-
kW-mo/yr
|
- | - | |
06 | 2.3212: Optimize plant power factor | $3,156 | $5,517 | - | - | $3,156 | - | |
07 | 2.6231: Utilize controls to operate equipment only when needed | $1,452 | $2,550 |
$1,452
37,808
kWh
|
- | - | - | |
08 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $6,589 | $21,750 |
$4,797
125,147
kWh
|
$1,792
-
kW-mo/yr
|
- | - | |
09 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $1,339 | $1,339 |
$989
25,791
kWh
|
$350
-
kW-mo/yr
|
- | - | |
10 | 3.5313: Increase amount of waste recovered for resale | $2,606 | - | - | - | - |
$2,606
-
lb
|
|
11 | 3.5315: Lease / purchase baler; sell cardboard to recycler | $2,850 | $250 | - | - | - |
$2,850
-
lb
|
|
TOTAL RECOMMENDED | $34,278 | $35,345 |
$19,676
513,774
kWh
|
$5,990
-
kW-mo/yr
|
$3,156 |
$5,456
-
lb
|
||
TOTAL IMPLEMENTED | $26,417 | $33,995 |
$17,898
467,174
kWh
|
$5,363
-
kW-mo/yr
|
$3,156 | - | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Solid Waste (non-haz) Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs