Assessment Year | 1993 |
---|---|
Principal Product | Glass Hard Disks |
NAICS |
n/a
|
SIC | 3695: Magnetic And Optical Recording Media |
Sales Range | $10 M to 50M |
# of Employees | 100 |
Plant Area |
60,000
ft2
|
Annual Production | 1,800,000
pieces
|
Production Hrs. Annual | 8,736
hrs
|
Location (State) | California |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $503,886 | 5,402,403 |
kWh
|
$0.093 |
Natural Gas | $19,577 | 3,408 |
MMBtu
|
$5.74 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $81,794 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $15,247 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Natural Gas Savings |
---|---|---|---|---|---|---|
01 | 2.2422: Use waste heat from hot flue gases to generate steam | $2,532 | $5,410 |
$2,532
27,257
kWh
|
- | |
02 | 2.4221: Install compressor air intakes in coolest locations | $700 | $130 |
$700
7,620
kWh
|
- | |
03 | 2.2511: Insulate bare equipment | $214 | $262 | - |
$214
-
MMBtu
|
|
04 | 2.1311: Replace electrically-operated equipment with fossil fuel equipment | $36,892 | $31,700 |
$49,003
525,498
kWh
|
$(-12,111.0)
-
MMBtu
|
|
05 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $4,713 | $9,277 |
$4,713
50,410
kWh
|
- | |
06 | 2.4133: Use most efficient type of electric motors | $8,002 | $4,553 |
$8,002
85,873
kWh
|
- | |
07 | 2.8114: Change rate schedules or other changes in utility service | $28,741 | $60,000 |
$28,741
-
kWh
|
- | |
TOTAL RECOMMENDED | $81,794 | $111,332 |
$93,691
696,658
kWh
|
$(-11,897.0)
-
MMBtu
|
||
TOTAL IMPLEMENTED | $15,247 | $19,240 |
$15,247
163,540
kWh
|
- | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Natural Gas Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs