| Assessment Year | 2026 |
|---|---|
| Principal Product | Wooden Cabinets |
| NAICS | 337110: Wood Kitchen Cabinet and Countertop Manufacturing |
| SIC | 2434: Wood Kitchen Cabinets |
| Sales Range | $10 M to 50M |
| # of Employees | 250 |
| Plant Area |
150,000
ft2
|
| Annual Production | 150,000
units
|
| Production Hrs. Annual | 4,000
hrs
|
| Location (State) | California |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $119,701 | 583,977 |
kWh
|
$0.20 |
| Electricity Demand | $47,177 | 2,829 |
kW-mo/yr
|
$16.68 |
| Electricity Fees | $5,812 | - |
|
- |
| TOTAL YEARLY COSTS | $172,690 | |||
| RECOMMENDED SAVINGS* | $277,353 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | - | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings |
|---|---|---|---|---|---|---|
| 01 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $187 | $762 |
$151
734
kWh
|
$37
-
kW-mo/yr
|
|
| 02 | 2.4231: Reduce the pressure of compressed air to the minimum required | $1,294 | - |
$1,294
5,330
kWh
|
- | |
| 03 | 2.4223: Install direct acting units in place of compressed air pressure system in safety system | $922 | $1,000 |
$922
4,495
kWh
|
- | |
| 04 | 2.4223: Install direct acting units in place of compressed air pressure system in safety system | $2,072 | $2,000 |
$2,072
10,108
kWh
|
- | |
| 05 | 2.4239: Eliminate or reduce compressed air usage | $3,579 | $4,156 |
$3,579
17,459
kWh
|
- | |
| 06 | 2.4133: Use most efficient type of electric motors | $26,086 | $12,918 |
$20,588
100,429
kWh
|
$5,498
-
kW-mo/yr
|
|
| 07 | 2.9114: Use solar heat to make electricty | $117,149 | $276,500 |
$87,125
425,000
kWh
|
$30,024
-
kW-mo/yr
|
|
| 08 | 2.3141: Use battery storage for demand control | $43,016 | $105,896 |
$(-4,522.1)
(-22,059)
kWh
|
$47,538
-
kW-mo/yr
|
|
| 09 | 2.4231: Reduce the pressure of compressed air to the minimum required | $30,685 | - |
$27,347
133,400
kWh
|
$3,338
-
kW-mo/yr
|
|
| 10 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $26,256 | $13,966 |
$21,104
102,948
kWh
|
$5,152
-
kW-mo/yr
|
|
| 11 | 2.2511: Insulate bare equipment | $23,068 | $6,000 |
$18,542
90,450
kWh
|
$4,526
-
kW-mo/yr
|
|
| 12 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $3,040 | $2,389 |
$2,444
11,920
kWh
|
$596
-
kW-mo/yr
|
|
| TOTAL RECOMMENDED | $277,353 | $425,588 |
$180,645
880,215
kWh
|
$96,708
-
kW-mo/yr
|
||
| TOTAL IMPLEMENTED | - | - | - | - | ||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs