| Assessment Year | 2026 |
|---|---|
| Principal Product | Fabric Printing |
| NAICS | 313310: Textile and Fabric Finishing Mills |
| SIC | 2269: Finishers of Textiles, Not elsewhere Classified |
| Sales Range | $1 M to 5M |
| # of Employees | 16 |
| Plant Area |
94,000
ft2
|
| Annual Production | 3,000
thousand feet
|
| Production Hrs. Annual | 2,250
hrs
|
| Location (State) | California |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $51,603 | 250,080 |
kWh
|
$0.21 |
| Electricity Demand | $40,297 | 2,856 |
kW-mo/yr
|
$14.11 |
| Electricity Fees | $12,894 | - |
|
- |
| Natural Gas | $84,298 | 9,686 |
MMBtu
|
$8.70 |
| TOTAL YEARLY COSTS | $189,092 | |||
| RECOMMENDED SAVINGS* | $142,373 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | - | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings |
|---|---|---|---|---|---|---|---|
| 01 | 2.2121: Increase amount of condensate returned | $19,217 | $12,000 |
$14,080
68,252
kWh
|
$5,136
-
kW-mo/yr
|
- | |
| 02 | 2.2414: Use waste heat from hot flue gases to preheat | $1,975 | $1,671 | - | - |
$1,975
-
MMBtu
|
|
| 03 | 2.2135: Repair and eliminate steam leaks | $2,690 | $600 | - | - |
$2,690
-
MMBtu
|
|
| 04 | 2.3131: Reschedule plant operations or reduce load to avoid peaks | $1,200 | - | - |
$1,200
-
kW-mo/yr
|
- | |
| 05 | 2.3132: Recharge batteries on during off-peak demand periods | $2,048 | - | - |
$2,048
-
kW-mo/yr
|
- | |
| 06 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $100 | $847 |
$72
350
kWh
|
$28
-
kW-mo/yr
|
- | |
| 07 | 2.4223: Install direct acting units in place of compressed air pressure system in safety system | $1,728 | $3,200 |
$1,728
8,376
kWh
|
- | - | |
| 08 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $8,172 | $12,660 |
$5,988
29,025
kWh
|
$2,184
-
kW-mo/yr
|
- | |
| 09 | 2.4133: Use most efficient type of electric motors | $16,055 | $85,261 |
$10,802
52,360
kWh
|
$5,253
-
kW-mo/yr
|
- | |
| 10 | 2.9114: Use solar heat to make electricty | $67,845 | $178,000 |
$52,607
255,000
kWh
|
$15,239
-
kW-mo/yr
|
- | |
| 11 | 2.3141: Use battery storage for demand control | $21,343 | $76,800 |
$(-2,785.1)
(-13,500)
kWh
|
$24,128
-
kW-mo/yr
|
- | |
| TOTAL RECOMMENDED | $142,373 | $371,039 |
$82,492
399,863
kWh
|
$55,217
-
kW-mo/yr
|
$4,665
-
MMBtu
|
||
| TOTAL IMPLEMENTED | - | - | - | - | - | ||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs