| Assessment Year | 2026 |
|---|---|
| Principal Product | Commercial Pringing |
| NAICS | 323111: Commercial Printing (except Screen and Books) |
| SIC | 2752: Commercial Printing, Lithographic |
| Sales Range | $10 M to 50M |
| # of Employees | 52 |
| Plant Area |
28,000
ft2
|
| Annual Production | 100,000,000
units
|
| Production Hrs. Annual | 4,590
hrs
|
| Location (State) | California |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $77,939 | 486,238 |
kWh
|
$0.16 |
| Electricity Demand | $227,838 | 3,400 |
kW-mo/yr
|
$67.01 |
| Electricity Fees | $21,559 | - |
|
- |
| TOTAL YEARLY COSTS | $327,336 | |||
| RECOMMENDED SAVINGS* | $596,601 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | - | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings |
|---|---|---|---|---|---|---|
| 01 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $5,977 | $5,475 |
$2,854
17,806
kWh
|
$3,123
-
kW-mo/yr
|
|
| 02 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $8,959 | $7,750 |
$4,281
26,708
kWh
|
$4,677
-
kW-mo/yr
|
|
| 03 | 2.4223: Install direct acting units in place of compressed air pressure system in safety system | $1,103 | $5,179 |
$1,103
6,881
kWh
|
- | |
| 04 | 2.9114: Use solar heat to make electricty | $301,993 | $404,796 |
$109,004
680,000
kWh
|
$192,989
-
kW-mo/yr
|
|
| 05 | 2.3141: Use battery storage for demand control | $242,570 | $278,520 |
$(-9,521.8)
(-59,400)
kWh
|
$252,092
-
kW-mo/yr
|
|
| 06 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $64 | $233 |
$27
169
kWh
|
$37
-
kW-mo/yr
|
|
| 07 | 2.4231: Reduce the pressure of compressed air to the minimum required | $1,161 | - |
$1,161
7,241
kWh
|
- | |
| 08 | 2.7234: Use heat pump for space conditioning | $15,399 | $29,800 |
$7,358
45,900
kWh
|
$8,041
-
kW-mo/yr
|
|
| 09 | 2.4221: Install compressor air intakes in coolest locations | $19,376 | $4,825 |
$9,257
57,750
kWh
|
$10,119
-
kW-mo/yr
|
|
| TOTAL RECOMMENDED | $596,601 | $736,578 |
$125,524
783,055
kWh
|
$471,077
-
kW-mo/yr
|
||
| TOTAL IMPLEMENTED | - | - | - | - | ||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs