| Assessment Year | 2026 |
|---|---|
| Principal Product | Plated Metal Sheets |
| NAICS | 332813: Electroplating, Plating, Polishing, Anodizing, and Coloring |
| SIC | 3471: Electroplating, Plating, Polishing, Anodizing, and Coloring |
| Sales Range | $100 M to 500M |
| # of Employees | 30 |
| Plant Area |
12,000
ft2
|
| Annual Production | 1,000,000
units
|
| Production Hrs. Annual | 4,625
hrs
|
| Location (State) | California |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | ||
|---|---|---|---|---|---|
| Electricity Usage | $76,645 | 485,897 |
kWh
|
$0.16 | |
| Electricity Demand | $145,165 | 2,580 |
kW-mo/yr
|
$56.27 | |
| Electricity Fees | $16,652 | - |
|
- | |
| Natural Gas | $32,047 | 2,052 |
MMBtu
|
$15.62 | |
| Waste Disposal Costs | |||||
| Water Usage | $3,132 | 250 |
Tgal
|
$12.53 | |
| TOTAL YEARLY COSTS | $273,641 | ||||
| RECOMMENDED SAVINGS* | $355,164 |
See individual recommendations below
*Non-energy impacts included in savings.
|
|||
| IMPLEMENTED SAVINGS* | - | ||||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Water Usage Savings |
|---|---|---|---|---|---|---|---|---|
| 01 | 2.2695: Use cascade system of recirculating during cold weather to avoid sub-cooling | $16,696 | $2,250 | - | - |
$15,652
-
MMBtu
|
$1,044
-
Tgal
|
|
| 02 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $4,062 | $5,475 |
$1,443
9,150
kWh
|
$2,619
-
kW-mo/yr
|
- | - | |
| 03 | 2.9114: Use solar heat to make electricty | $90,071 | $134,797 |
$36,109
228,970
kWh
|
$53,963
-
kW-mo/yr
|
- | - | |
| 04 | 2.3141: Use battery storage for demand control | $150,344 | $206,780 |
$(-6,818.2)
(-43,235)
kWh
|
$157,162
-
kW-mo/yr
|
- | - | |
| 05 | 2.4223: Install direct acting units in place of compressed air pressure system in safety system | $335 | $600 |
$335
2,122
kWh
|
- | - | - | |
| 06 | 2.4226: Use / purchase optimum sized compressor | $826 | $1,230 |
$826
5,240
kWh
|
- | - | - | |
| 07 | 2.4231: Reduce the pressure of compressed air to the minimum required | $1,060 | - |
$1,060
6,719
kWh
|
- | - | - | |
| 08 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $357 | $1,271 |
$182
1,157
kWh
|
$174
-
kW-mo/yr
|
- | - | |
| 09 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $10,897 | $11,400 |
$5,659
35,883
kWh
|
$5,239
-
kW-mo/yr
|
- | - | |
| 10 | 2.3131: Reschedule plant operations or reduce load to avoid peaks | $19,921 | - | - |
$19,921
-
kW-mo/yr
|
- | - | |
| 11 | 2.4133: Use most efficient type of electric motors | $34,215 | $9,487 |
$15,084
95,646
kWh
|
$19,132
-
kW-mo/yr
|
- | - | |
| 12 | 2.7232: Replace existing hvac unit with high efficiency model | $3,172 | $5,500 |
$1,872
11,872
kWh
|
$1,300
-
kW-mo/yr
|
- | - | |
| 13 | 2.1221: Replace obsolete burners with more efficient ones | $6,945 | $8,300 | - | - |
$6,945
-
MMBtu
|
- | |
| 14 | 2.7234: Use heat pump for space conditioning | $16,262 | $29,800 |
$7,540
47,813
kWh
|
$8,722
-
kW-mo/yr
|
- | - | |
| TOTAL RECOMMENDED | $355,164 | $416,890 |
$63,291
401,337
kWh
|
$268,232
-
kW-mo/yr
|
$22,597
-
MMBtu
|
$1,044
-
Tgal
|
||
| TOTAL IMPLEMENTED | - | - | - | - | - | - | ||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Water Usage Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs