Assessment Year | 2025 |
---|---|
Principal Product | Packaging |
NAICS | 322211: Corrugated and Solid Fiber Box Manufacturing |
SIC | 2653: Corrugated and Solid Fiber Boxes |
Sales Range | $50 M to 100M |
# of Employees | 80 |
Plant Area |
129,911
ft2
|
Annual Production | 100,000,000
units
|
Production Hrs. Annual | 4,250
hrs
|
Location (State) | California |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $374,245 | 1,960,139 |
kWh
|
$0.19 |
Electricity Demand | $489,061 | 7,182 |
kW-mo/yr
|
$68.09 |
TOTAL YEARLY COSTS | $863,306 | |||
RECOMMENDED SAVINGS* | $1,079,411 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | - |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings |
---|---|---|---|---|---|---|
01 | 2.9114: Use solar heat to make electricty | $672,356 | $643,693 |
$267,802
1,402,840
kWh
|
$404,554
-
kW-mo/yr
|
|
02 | 2.3141: Use battery storage for demand control | $314,276 | $12,865 |
$(-26,953.0)
(-141,189)
kWh
|
$341,229
-
kW-mo/yr
|
|
03 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $11,060 | $4,266 |
$4,721
24,730
kWh
|
$6,339
-
kW-mo/yr
|
|
04 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $8,102 | $3,252 |
$3,911
20,489
kWh
|
$4,190
-
kW-mo/yr
|
|
05 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $33,214 | $18,590 |
$9,442
49,460
kWh
|
$23,772
-
kW-mo/yr
|
|
06 | 2.3131: Reschedule plant operations or reduce load to avoid peaks | $12,191 | - | - |
$12,191
-
kW-mo/yr
|
|
07 | 2.4231: Reduce the pressure of compressed air to the minimum required | $6,623 | $500 |
$6,623
34,691
kWh
|
- | |
08 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $1,107 | $2,287 |
$534
2,797
kWh
|
$573
-
kW-mo/yr
|
|
09 | 2.4239: Eliminate or reduce compressed air usage | $3,465 | $3,200 |
$3,465
18,149
kWh
|
- | |
10 | 2.4221: Install compressor air intakes in coolest locations | $6,427 | $3,278 |
$3,103
16,252
kWh
|
$3,324
-
kW-mo/yr
|
|
11 | 2.7232: Replace existing hvac unit with high efficiency model | $10,593 | $35,000 |
$7,676
40,207
kWh
|
$2,917
-
kW-mo/yr
|
|
TOTAL RECOMMENDED | $1,079,411 | $726,931 |
$280,323
1,468,426
kWh
|
$799,089
-
kW-mo/yr
|
||
TOTAL IMPLEMENTED | - | - | - | - | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs