| Assessment Year | 2024 |
|---|---|
| Principal Product | Fasteners |
| NAICS | 339993: Fastener, Button, Needle, and Pin Manufacturing |
| SIC | 3965: Fasteners, Buttons, Needles, and Pins |
| Sales Range | $100 M to 500M |
| # of Employees | 400 |
| Plant Area |
179,000
ft2
|
| Annual Production | 25,000,000
pieces
|
| Production Hrs. Annual | 5,967
hrs
|
| Location (State) | California |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $1,108,558 | 10,340,808 |
kWh
|
$0.11 |
| Electricity Demand | $777,479 | 19,296 |
kW-mo/yr
|
$40.29 |
| Electricity Fees | $59,503 | - |
|
- |
| Natural Gas | $172,433 | 35,701 |
MMBtu
|
$4.83 |
| TOTAL YEARLY COSTS | $2,117,973 | |||
| RECOMMENDED SAVINGS* | $2,230,054 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | $51,738 | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings |
|---|---|---|---|---|---|---|---|
| 01 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $10,802 | $16,517 |
$7,083
66,073
kWh
|
$3,719
-
kW-mo/yr
|
- | |
| 02 | 2.9114: Use solar heat to make electricty | $742,364 | $1,089,169 |
$295,065
2,752,470
kWh
|
$447,299
-
kW-mo/yr
|
- | |
| 03 | 2.3141: Use battery storage for demand control | $657,585 | - |
$(-44,227.0)
(-412,560)
kWh
|
$701,812
-
kW-mo/yr
|
- | |
| 04 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $142,164 | $183,960 |
$73,099
681,891
kWh
|
$69,065
-
kW-mo/yr
|
- | |
| 05 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $52,035 | $39,675 |
$29,634
276,431
kWh
|
$22,401
-
kW-mo/yr
|
- | |
| 06 | 2.3131: Reschedule plant operations or reduce load to avoid peaks | $570,483 | - | - |
$570,483
-
kW-mo/yr
|
- | |
| 07 | 2.4133: Use most efficient type of electric motors | $40,936 | $125,410 |
$23,313
217,469
kWh
|
$17,623
-
kW-mo/yr
|
- | |
| 08 | 2.2414: Use waste heat from hot flue gases to preheat | $916 | $3,000 | - | - |
$916
-
MMBtu
|
|
| 09 | 2.4223: Install direct acting units in place of compressed air pressure system in safety system | $12,769 | $40,200 |
$12,769
119,111
kWh
|
- | - | |
| TOTAL RECOMMENDED | $2,230,054 | $1,497,931 |
$396,736
3,700,885
kWh
|
$1,832,402
-
kW-mo/yr
|
$916
-
MMBtu
|
||
| TOTAL IMPLEMENTED | $51,738 | $141,927 |
$30,396
283,542
kWh
|
$21,342
-
kW-mo/yr
|
- | ||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs