Assessment Year | 2023 |
---|---|
Principal Product | Metal Doors and Windows |
NAICS | 332321: Metal Window and Door Manufacturing |
SIC | 3444: Sheet Metal Work |
Sales Range | $10 M to 50M |
# of Employees | 80 |
Plant Area |
40,000
ft2
|
Annual Production | 100,000
units
|
Production Hrs. Annual | 4,250
hrs
|
Location (State) | California |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | ||
---|---|---|---|---|---|
Electricity Usage | $96,909 | 1,061,490 |
kWh
|
$0.091 | |
Electricity Demand | $27,256 | 3,233 |
kW-mo/yr
|
$8.43 | |
Electricity Fees | $5,614 | - |
|
- | |
Natural Gas | $10,011 | 363 |
MMBtu
|
$27.60 | |
Waste Disposal Costs | |||||
Other Liquid (haz) | $62,110 | 898 |
gal
|
$69.15 | |
TOTAL YEARLY COSTS | $201,900 | ||||
RECOMMENDED SAVINGS* | $75,535 |
See individual recommendations below
*Non-energy impacts included in savings.
|
|||
IMPLEMENTED SAVINGS* | - |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Other Liquid (haz) Savings | Personnel Changes Savings |
---|---|---|---|---|---|---|---|---|
01 | 2.4223: Install direct acting units in place of compressed air pressure system in safety system | $1,793 | $2,300 |
$1,793
19,644
kWh
|
- | - | - | |
02 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $2,958 | $14,573 |
$2,193
24,016
kWh
|
$730
-
kW-mo/yr
|
- | $35 | |
03 | 3.1121: Use more efficient adhesive applicators | $14,334 | $2,200 | - | - |
$14,334
-
gal
|
- | |
04 | 2.4231: Reduce the pressure of compressed air to the minimum required | $1,070 | $500 |
$1,070
11,724
kWh
|
- | - | - | |
05 | 2.9114: Use solar heat to make electricty | $44,733 | $141,268 |
$32,594
357,000
kWh
|
$12,139
-
kW-mo/yr
|
- | - | |
06 | 2.3141: Use battery storage for demand control | $4,384 | - |
$(-4,521.0)
(-49,518)
kWh
|
$8,905
-
kW-mo/yr
|
- | - | |
07 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $325 | $847 |
$255
2,787
kWh
|
$71
-
kW-mo/yr
|
- | - | |
08 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $1,872 | $2,290 |
$1,389
15,218
kWh
|
$483
-
kW-mo/yr
|
- | - | |
09 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $4,066 | $5,607 |
$3,184
34,869
kWh
|
$882
-
kW-mo/yr
|
- | - | |
TOTAL RECOMMENDED | $75,535 | $169,585 |
$37,956
415,740
kWh
|
$23,210
-
kW-mo/yr
|
$14,334
-
gal
|
$35 | ||
TOTAL IMPLEMENTED | - | - | - | - | - | - | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Other Liquid (haz) Savings | Personnel Changes Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs