Assessment Year 2023
Principal Product Dripline, Gardening Tubing
NAICS 333111: Farm Machinery and Equipment Manufacturing
SIC 3523: Farm Machinery and Equipment
Sales Range $10
M
to 50
M
# of Employees 43
Plant Area 40,320
ft2
Annual Production 17,276,000
units
Production Hrs. Annual 6,000
hrs
Location (State) California

Facility Energy Cost and Usage

Source Yearly Cost Usage
Electricity Usage $197,149 814,464
kWh
Electricity Demand $72,622 3,503
kW-mo/yr
Electricity Fees $2,704 -
TOTAL YEARLY COSTS $272,475
RECOMMENDED SAVINGS* $36,236 *Non-energy impacts included in savings.
IMPLEMENTED SAVINGS* $754

Recommendations

# Description Yearly Savings* Imp'd Cost* Status Electricity Usage Savings Electricity Demand Savings
01 2.4133: Use most efficient type of electric motors $2,583 $10,494 $2,133
8,804
kWh
$450
-
kW-mo/yr
02 2.3141: Use battery storage for demand control $15,108 $70,650 $(-2,445.0)
(-10,100)
kWh
$17,553
-
kW-mo/yr
03 2.7134: Use photocell controls $754 $1,124 $754
3,116
kWh
-
04 2.4223: Install direct acting units in place of compressed air pressure system in safety system $3,553 $3,535 $3,553
14,676
kWh
-
05 2.4146: Use adjustable frequency drive or multiple speed motors on existing system $10,208 $16,000 $8,716
36,000
kWh
$1,492
-
kW-mo/yr
06 2.4146: Use adjustable frequency drive or multiple speed motors on existing system $928 $2,934 $780
3,222
kWh
$148
-
kW-mo/yr
07 2.2511: Insulate bare equipment $1,509 $4,973 $1,262
5,213
kWh
$247
-
kW-mo/yr
08 2.4221: Install compressor air intakes in coolest locations $1,593 $4,339 $1,507
6,225
kWh
$86
-
kW-mo/yr
TOTAL RECOMMENDED $36,236 $114,049 $16,260
67,156
kWh
$19,976
-
kW-mo/yr
TOTAL IMPLEMENTED $754 $1,124 $754
3,116
kWh
-
Yearly Savings* Imp'd Cost* Electricity Usage Savings Electricity Demand Savings
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs