Assessment Year | 2023 |
---|---|
Principal Product | Printed Labels, Flexible Packaging Film, Shrink Sleeves |
NAICS | 323111: Commercial Printing (except Screen and Books) |
SIC | 2759: Commercial Printing, Not Elsewhere Classified |
Sales Range | $5 M to 10M |
# of Employees | 25 |
Plant Area |
35,000
ft2
|
Annual Production | 800
units
|
Production Hrs. Annual | 2,167
hrs
|
Location (State) | California |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $85,115 | 662,473 |
kWh
|
$0.13 |
Electricity Demand | $46,069 | 3,731 |
kW-mo/yr
|
$12.35 |
Electricity Fees | $712 | - |
|
- |
TOTAL YEARLY COSTS | $131,896 | |||
RECOMMENDED SAVINGS* | $80,619 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | - |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings |
---|---|---|---|---|---|---|---|
01 | 2.9114: Use solar heat to make electricty | $67,963 | $332,640 |
$41,287
321,300
kWh
|
$26,676
-
kW-mo/yr
|
- | |
02 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $750 | $1,100 |
$438
3,409
kWh
|
$312
-
kW-mo/yr
|
- | |
03 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $1,372 | $4,320 |
$739
5,746
kWh
|
$601
-
kW-mo/yr
|
$32 | |
04 | 2.4221: Install compressor air intakes in coolest locations | $386 | $976 |
$386
3,004
kWh
|
- | - | |
05 | 2.7228: Avoid introducing hot, humid, or dirty air into hvac system | $9,930 | $10,320 |
$7,115
55,366
kWh
|
$2,815
-
kW-mo/yr
|
- | |
06 | 2.4224: Upgrade controls on compressors | $218 | - |
$218
1,700
kWh
|
- | - | |
TOTAL RECOMMENDED | $80,619 | $349,356 |
$50,183
390,525
kWh
|
$30,404
-
kW-mo/yr
|
$32 | ||
TOTAL IMPLEMENTED | - | - | - | - | - | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs