Assessment Year | 2021 |
---|---|
Principal Product | Flour |
NAICS | 311211: Flour Milling |
SIC | 2041: Flour and Other Grain Mill Products |
Sales Range | $50 M to 100M |
# of Employees | 41 |
Plant Area |
80,000
ft2
|
Annual Production | 214,800
ton
|
Production Hrs. Annual | 8,592
hrs
|
Location (State) | California |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | ||
---|---|---|---|---|---|
Electricity Usage | $1,375,636 | 13,576,357 |
kWh
|
$0.10 | |
Electricity Demand | $696,959 | 28,691 |
kW-mo/yr
|
$24.29 | |
Electricity Fees | $181,724 | - |
|
- | |
Waste Disposal Costs | |||||
Water Usage | $3,619 | 891 |
Tgal
|
$4.06 | |
TOTAL YEARLY COSTS | $2,257,938 | ||||
RECOMMENDED SAVINGS* | $66,386 |
See individual recommendations below
*Non-energy impacts included in savings.
|
|||
IMPLEMENTED SAVINGS* | - |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | One-time Revenue or Avoided Cost Savings |
---|---|---|---|---|---|---|---|
01 | 2.3132: Recharge batteries on during off-peak demand periods | $26,888 | $500 |
$7,604
423,561
kWh
|
$19,284
-
kW-mo/yr
|
- | |
02 | 2.7232: Replace existing hvac unit with high efficiency model | $17,809 | $38,800 |
$14,230
140,491
kWh
|
$3,579
-
kW-mo/yr
|
- | |
03 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $13,885 | $2,100 |
$11,893
117,404
kWh
|
$1,992
-
kW-mo/yr
|
- | |
04 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $2,753 | $568 |
$2,061
20,435
kWh
|
$692
-
kW-mo/yr
|
- | |
05 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $3,289 | $2,741 |
$2,387
23,573
kWh
|
$799
-
kW-mo/yr
|
$103 | |
06 | 2.7111: Reduce illumination to minimum necessary levels | $794 | $760 |
$595
5,877
kWh
|
$199
-
kW-mo/yr
|
- | |
07 | 2.4221: Install compressor air intakes in coolest locations | $481 | $706 |
$413
4,077
kWh
|
$68
-
kW-mo/yr
|
- | |
08 | 2.4133: Use most efficient type of electric motors | $487 | $540 |
$365
3,599
kWh
|
$122
-
kW-mo/yr
|
- | |
TOTAL RECOMMENDED | $66,386 | $46,715 |
$39,548
739,017
kWh
|
$26,735
-
kW-mo/yr
|
$103 | ||
TOTAL IMPLEMENTED | - | - | - | - | - | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | One-time Revenue or Avoided Cost Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs