Assessment Year | 2019 |
---|---|
Principal Product | Windows and Doors |
NAICS | 326199: All Other Plastics Product Manufacturing |
SIC | 3089: Plastics Products, Not Elsewhere Classified |
Sales Range | $100 M to 500M |
# of Employees | 450 |
Plant Area |
185,000
ft2
|
Annual Production | 286,800
units
|
Production Hrs. Annual | 5,720
hrs
|
Location (State) | California |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $262,098 | 3,745,477 |
kWh
|
$0.070 |
Electricity Demand | $248,489 | 9,158 |
kW-mo/yr
|
$27.13 |
Electricity Fees | $9,293 | - |
|
- |
Natural Gas | $29,312 | 3,812 |
MMBtu
|
$7.69 |
Other Gas | $180 | 1 |
MMBtu
|
$180.00 |
TOTAL YEARLY COSTS | $549,372 | |||
RECOMMENDED SAVINGS* | $97,018 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $95,075 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | One-time Revenue or Avoided Cost Savings |
---|---|---|---|---|---|---|---|
01 | 2.7232: Replace existing hvac unit with high efficiency model | $57,437 | $117,800 |
$39,565
565,228
kWh
|
$17,872
-
kW-mo/yr
|
- | |
02 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $25,164 | $24,783 |
$13,478
192,557
kWh
|
$10,963
-
kW-mo/yr
|
$723 | |
03 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $4,548 | $17,875 |
$2,509
35,836
kWh
|
$2,039
-
kW-mo/yr
|
- | |
04 | 2.4231: Reduce the pressure of compressed air to the minimum required | $2,460 | - |
$2,460
35,139
kWh
|
- | - | |
05 | 2.7135: Install occupancy sensors | $1,882 | $330 |
$1,882
26,879
kWh
|
- | - | |
06 | 2.4324: Replace hydraulic / pneumatic equipment with electric equipment | $1,834 | $2,795 |
$1,834
26,201
kWh
|
- | - | |
07 | 2.7261: Install timers and/or thermostats | $1,750 | $350 |
$1,750
24,999
kWh
|
- | - | |
08 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $1,943 | $750 |
$1,599
22,781
kWh
|
$344
-
kW-mo/yr
|
- | |
TOTAL RECOMMENDED | $97,018 | $164,683 |
$65,077
929,620
kWh
|
$31,218
-
kW-mo/yr
|
$723 | ||
TOTAL IMPLEMENTED | $95,075 | $163,933 |
$63,478
906,839
kWh
|
$30,874
-
kW-mo/yr
|
$723 | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | One-time Revenue or Avoided Cost Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs