Assessment Year | 2009 |
---|---|
Principal Product | louvers |
NAICS | 332322: Sheet Metal Work Manufacturing |
SIC | 3444: Sheet Metal Work |
Sales Range | $10 M to 50M |
# of Employees | 125 |
Plant Area |
80,000
ft2
|
Annual Production | 150,000
pieces
|
Production Hrs. Annual | 2,152
hrs
|
Location (State) | California |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $73,641 | 671,477 |
kWh
|
$0.11 |
Electricity Demand | $25,337 | 2,635 |
kW-mo/yr
|
$9.62 |
Electricity Fees | $9,969 | - |
|
- |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $4,494 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $205 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings |
---|---|---|---|---|---|---|
01 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $1,279 | $5,868 |
$1,279
11,665
kWh
|
- | |
02 | 2.7135: Install occupancy sensors | $205 | $246 |
$205
1,872
kWh
|
- | |
03 | 2.7261: Install timers and/or thermostats | $1,671 | $500 |
$1,671
11,700
kWh
|
- | |
04 | 2.4133: Use most efficient type of electric motors | $1,141 | $4,207 |
$763
6,960
kWh
|
$378
-
kW-mo/yr
|
|
05 | 2.4231: Reduce the pressure of compressed air to the minimum required | $198 | - |
$198
1,805
kWh
|
- | |
TOTAL RECOMMENDED | $4,494 | $10,821 |
$4,116
34,002
kWh
|
$378
-
kW-mo/yr
|
||
TOTAL IMPLEMENTED | $205 | $246 |
$205
1,872
kWh
|
- |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs