Assessment Year | 2015 |
---|---|
Principal Product | store furnatures and fixtures |
NAICS | 337215: Showcase, Partition, Shelving, and Locker Manufacturing |
SIC | 2541: Wood Office and Store Fixtures, Partitions, Shelving, and Lockers |
Sales Range | $10 M to 50M |
# of Employees | 200 |
Plant Area |
96,000
ft2
|
Annual Production | 200,000
pieces
|
Production Hrs. Annual | 8,600
hrs
|
Location (State) | Missouri |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $216,535 | 3,070,061 |
kWh
|
$0.071 |
Electricity Demand | $26,439 | 9,968 |
kW-mo/yr
|
$2.65 |
Natural Gas | $18,693 | 2,805 |
MMBtu
|
$6.66 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $72,558 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | - |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings |
---|---|---|---|---|---|---|---|
01 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $28,665 | $105,525 |
$27,235
386,140
kWh
|
$1,430
-
kW-mo/yr
|
- | |
02 | 2.7135: Install occupancy sensors | $17,740 | $1,500 |
$17,740
251,550
kWh
|
- | - | |
03 | 2.6212: Turn off equipment during breaks, reduce operating time | $1,335 | - |
$1,335
18,926
kWh
|
- | - | |
04 | 2.4221: Install compressor air intakes in coolest locations | $6,584 | $6,500 |
$6,255
88,682
kWh
|
$329
-
kW-mo/yr
|
- | |
05 | 3.1161: Eliminate/reduce an operation | $736 | - |
$691
9,804
kWh
|
$45
-
kW-mo/yr
|
- | |
06 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $13,904 | $1,210 |
$13,212
187,322
kWh
|
$692
-
kW-mo/yr
|
- | |
07 | 2.4239: Eliminate or reduce compressed air usage | $2,409 | $2,500 |
$2,245
31,824
kWh
|
$164
-
kW-mo/yr
|
- | |
08 | 2.7221: Lower temperature during the winter season and vice-versa | $1,185 | - |
$763
10,814
kWh
|
$42
-
kW-mo/yr
|
$380
-
MMBtu
|
|
TOTAL RECOMMENDED | $72,558 | $117,235 |
$69,476
985,062
kWh
|
$2,702
-
kW-mo/yr
|
$380
-
MMBtu
|
||
TOTAL IMPLEMENTED | - | - | - | - | - | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs