| Assessment Year | 2009 |
|---|---|
| Principal Product | Optical Rotary Encoders |
| NAICS | 335314: Relay and Industrial Control Manufacturing |
| SIC | 3625: Relays and Industrial Controls |
| Sales Range | $10 M to 50M |
| # of Employees | 72 |
| Plant Area |
33,600
ft2
|
| Annual Production | 275,000
pieces
|
| Production Hrs. Annual | 1,700
hrs
|
| Location (State) | California |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $86,549 | 968,284 |
kWh
|
$0.089 |
| Electricity Demand | $50,360 | 2,895 |
kW-mo/yr
|
$17.40 |
| Electricity Fees | $4,545 | - |
|
- |
| Natural Gas | $3,296 | 278 |
MMBtu
|
$11.86 |
| TOTAL YEARLY COSTS | - | |||
| RECOMMENDED SAVINGS* | $18,418 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | $11,611 | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings |
|---|---|---|---|---|---|---|---|
| 01 | 2.7232: Replace existing hvac unit with high efficiency model | $6,503 | $18,750 |
$6,503
45,990
kWh
|
- | - | |
| 02 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $4,780 | $7,974 |
$4,780
53,465
kWh
|
- | - | |
| 03 | 2.4226: Use / purchase optimum sized compressor | $3,009 | - |
$3,009
33,662
kWh
|
- | - | |
| 04 | 2.3131: Reschedule plant operations or reduce load to avoid peaks | $1,047 | - | - | - | $1,047 | |
| 05 | 2.7111: Reduce illumination to minimum necessary levels | $1,035 | $128 |
$451
5,040
kWh
|
$584
-
kW-mo/yr
|
- | |
| 06 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $910 | $1,000 |
$910
10,174
kWh
|
- | - | |
| 07 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $657 | $5,864 |
$340
3,802
kWh
|
$317
-
kW-mo/yr
|
- | |
| 08 | 2.7145: Install skylights | $323 | $1,470 |
$323
3,611
kWh
|
- | - | |
| 09 | 2.7135: Install occupancy sensors | $154 | $347 |
$154
1,727
kWh
|
- | - | |
| TOTAL RECOMMENDED | $18,418 | $35,533 |
$16,470
157,471
kWh
|
$901
-
kW-mo/yr
|
$1,047 | ||
| TOTAL IMPLEMENTED | $11,611 | $20,225 |
$11,027
96,593
kWh
|
$584
-
kW-mo/yr
|
- | ||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs